27
4.3 - Physical data 30XB with option 254 or 255 (continued)
30XB-850 to 1700 with option 254 or 255
30XB option 254/255
850
900
1000
1100
1200
1300
1400
1550
1700
Sound levels
Standard unit
Sound power
(1)
dB(A)
101
104
102
103
102
104
104
104
104
Sound pressure at 10 m
(2)
dB(A)
70
71
69
70
69
71
71
71
70
Unit + option 15
(3)
Sound power
(1)
dB(A)
97
99
98
98
98
100
99
100
100
Sound pressure at 10 m
(2)
dB(A)
65
66
65
65
65
67
65
67
66
Unit + option 15LS
(3)
Sound power
(1)
dB(A)
94
95
94
94
94
99
95
96
96
Sound pressure at 10 m
(2)
dB(A)
60
62
65
65
61
65
61
61
61
Unit + option 15LS+
(3)
Sound power
(1)
dB(A)
91
93
92
93
93
97
94
93
93
Sound pressure at 10 m
(2)
dB(A)
58
60
59
60
60
66
61
60
60
Dimensions
Standard unit
Length
mm
8380
9574
9574
11962
11962
11962
11962
9574/
4798
8380/
8380
Width
mm
2253
2253
2253
2253
2253
2253
2253
2253
2253
Height
mm
2297
2297
2297
2297
2297
2297
2297
2297
2297
Operating weight
(4)
Standard unit
kg
6414
7049
7253
8628
8761
9339
9416
3716/
7287
6464/
6464
Unit + option 15
(3)
kg
6745
7380
7584
8999
9132
9711
9788
3882/
7618
6794/
6794
Compressors
06T semi-hermetic screw compressor, 50 r/s
Circuit A
1
1
1
1
1
1
1
1
1
Circuit B
1
1
1
1
1
1
1
1
1
Circuit C
1
1
Circuit D
1
No. of control stages
Refrigerant for standard unit
(4)
R134a
Circuit A
kg
130
129
140
125
128
170
176
140
130
teqCO
2
185,9
184,5
200,2
178,8
183,0
243,1
251,7
200,2
185,9
Circuit C
kg
95
103
129
180
196
176
184
129
95
teqCO
2
135,9
147,3
184,5
257,4
280,3
251,7
263,1
184,5
135,9
Circuit B
kg
135,0
130,0
teqCO
2
193,1
185,9
Circuit D
kg
95,0
teqCO
2
135,9
Oil
Circuit A
l
27,6
27,6
27,6
27,6
36,0
36,0
36,0
27,6
27,6
Circuit B
l
23,5
27,6
27,6
36,0
36,0
36,0
36,0
27,6
23,5
Circuit C
l
27,6
27,6
Circuit D
l
23,5
(1) in dB ref=10
-12
W, ‘A’ weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). Measured in
accordance with ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20μPa, ‘A’ weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). For information,
calculated from the sound power Lw(A).
(3) Options : 15 = Low noise, 15LS = Very Low noise, 118a = DX freecooling option, 50= Heat recovery.
(4) Values are guidelines only. Refer to the unit name plate.
Eurovent certified
values
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS
Содержание AquaForce 30XB series
Страница 69: ......