33
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS
4.5 - Electrical data (continued)
30XBP from 1100 to 1500 (continued)
30XBP
1100
1200
1300
1400
1500
Maximum current (Un-10%)
(1)
Standard unit
Circuit 1
(a)
A
313
359
430
460
498
Circuit 2
(a)
A
457
498
460
495
498
Option 081
A
772
859
892
957
998
Unit + option 15LS
Circuit 1
(a)
A
306
352
420
450
487
Circuit 2
(a)
A
448
487
450
485
487
Option 081
584
630
657
702
736
Nominal start-up current
(3)
Standard unit
Circuit 1
(a)
A
580
580
619
619
618
Circuit 2
(a)
A
620
618
619
619
618
Option 081
A
923
962
965
995
997
Option 081 & Opt 25c
A
786
801,5
824
841,5
839,5
Unit + option 15LS
Circuit 1
(a)
A
573
573
609
609
607
Circuit 2
(a)
A
611
607
609
609
607
Option 081
A
907
944
945
975
975
Option 081 & Opt 25c
A
770
783,5
804
821,5
817,5
Maximum start-up current(Un)
(2)
Standard unit
Circuit 1
(a)
A
580
580
619
619
618
Circuit 2
(a)
A
620
618
619
619
618
Option 081
A
1030
1077
1075
1110
1112
Option 081 & Opt 25c
A
786
801,5
824
841,5
839,5
Unit + option 15LS
Circuit 1
(a)
A
573
573
609
609
607
Circuit 2
(a)
A
611
607
609
609
607
Option 081
A
1014
1059
1055
1090
1090
Option 081 & Opt 25c
A
770
783,5
804
821,5
817,5
(1) Values obtained at unit continuous maximum operating conditions (data given on the unit nameplate)
(2) Operating current of the smallest compressor(s) + fan c locked rotor current or reduced start-up current of the largest compressor.
(3) Standardised EUROVENT conditions, water-cooled exchanger water inlet/outlet = 12°C/7°C, outdoor air temperature = 35°C.
(a) When the machines are equipped with two power supplies, circuit 1 supplies the refrigerant circuit A and circuit 2 supplies the refrigerant circuit B or for units 30XBP1550