30
4.5 - Electrical data (continued)
30XB from 1100 to 1700
30XB
1100
1200
1300
1400
1500
1550
1700
Power circuit supply
Nominal voltage
V-ph-Hz
400-3-50
Voltage range
V
360-440
Control circuit supply
24 V via internal transformer
Maximum operating input power
(1)
Standard unit
kW
Circuit 1
(a)
kW
196
225
267
286
309
459
366
Circuit 2
(a)
kW
286
312
286
307
309
230
366
Option 081
kW
483
537
553
593
619
689
Unit + option 15LS
Circuit 1
(a)
kW
190
218
258
276
299
451
354
Circuit 2
(a)
kW
277
301
276
297
299
222
354
Option 081
kW
467
520
534
574
598
666
Power factor at maximum power
(1)
Standard unit
Displacement Power Factor (Cos Phi)
0,88
0,88
0,88
0,88
0,88
0,89
0,89
Unit + option 15LS
Displacement Power Factor (Cos Phi)
0,88
0,88
0,88
0,88
0,88
0,89
0,89
Nominal operating current draw
(2)
Standard unit
Circuit 1
(a)
A
258
274
341
356
390
543
446
Circuit 2
(a)
A
358
392
356
386
390
273
446
Option 081
A
616
666
697
742
780
820
Unit + option 15LS
Circuit 1
(a)
A
247
263
325
340
372
530
427
Circuit 2
(a)
A
344
374
340
370
372
260
427
Option 081
A
590
637
665
710
745
782
Maximum operating current draw (Un)
(1)
Standard unit
Circuit 1
(a)
A
320
366
440
470
509
740
593
Circuit 2
(a)
A
466
509
470
505
509
370
593
Option 081
A
788
877
912
977
1020
1113
Unit + option 15LS
Circuit 1
(a)
A
309
355
424
454
491
727
574
Circuit 2
(a)
A
452
491
454
489
491
357
574
Option 081
A
762
848
880
945
985
1074
(1) Values obtained at unit continuous maximum operating conditions (data given on the unit nameplate)
(2) Operating current of the smallest compressor(s) + fan c locked rotor current or reduced start-up current of the largest compressor.
(a) When the machines are equipped with two power supplies, circuit 1 supplies the refrigerant circuit A and circuit 2 supplies the refrigerant circuit B or for units 30XB1550
to 1700 units: Circuit 1 supplies circuits A and B, circuit 2 supplies circuits C and D.
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS