50
9.1 - Physical data,30XB & XBP units with heat reclaim condenser option
30XB &XBP heat reclaim mode
250
300
350
400
450
500
600
700
750
800
850
900
1000
Operating weight*
kg
3370
3404
3425
4102
4245
4601
5551
5782
6065
6382
6430
6805
7272
Condenser diameter
in
10
10
10
12
14
14
12+12 12+12 14+12 14+12 14+12 14+14 14+14
Refrigerant charge
Circuit A
kg
37
35
35
51
52
59
58
58
65
69
72
69
91
Circuit B
kg
39
37
37
37
37
36
59
62
58
65
63
76
89
Heat reclaim condenser
Flooded multi-pipe condenser
Water volume
l
38
38
38
55
68
68
55+55 55+55 68 + 55 68 + 55 68 + 55 68+68 68+68
Water connections
Type Victaulic
Nominal diameter
in
3
3
3
4
4
4
4
4
4
4
4
4
4
Actual outside diameter
mm
88,9
88,9
88,9
114,3
114,3
114,3
114,3
114,3
114,3
114,3
114,3
114,3
114,3
*
Weights are for guidance only
9.2 - Dimensions, clearances
9.2.1 - 30XB-250 to 350 - heat reclaim option
ATTENTION: The condenser connection sleeves are not
installed, but supplied with the unit. The sealing joints are in
the control box. The temperature sensors and the condenser
flow switch are wired and fixed in the machine. They must be
installed as described in the chapter “Condenser water
connections”.
NOTES:
-
Drawings are not contractually binding.
-
Before designing an installation, consult the certified
dimensional drawings, available on request.
-
For the positioning of the fixing points, weight
distribution and centre of gravity coordinates please
refer to the dimensional drawings.
-
If the installation includes several units or if this
(these) is (are) close to walls, please refer to chapters
3.11 - “Multiple chiller installation” and 3.12 -
“Distance to the wall” of this document to determine
the space required.
Legend
All dimensions are given in mm.
1
Required clearances for maintenance (see note)
2
Recommended space for evaporator tube removal
Water inlet for standard unit
For options 5, 6, 100A, 100C, 107 refer to the certified
drawing.
Water outlet
For options 5, 6, 100A, 100C, 107 refer to the certified
drawing.
Air outlet – do not obstruct
Power supply and control connection
A
Heat reclaim condenser
9 - HEAT RECLAIM CONDENSER OPTION (OPTION 50)