26
4.3 - Physical data 30XB with option 254 or 255 (continued)
30XB-250 to 800 with option 254 or 255 (continued)
30XB option 254/255
250
300
350
400
450
500
600
700
750
800
Capacity control
Touch Pilot, , Electronic Expansion Valve (EXV)
Minimum capacity
%
15
15
15
15
15
15
15
15
15
15
Air heat exchanger
Aluminum micro-channel coils (MCHE)
Fans
FLYING-BIRD 6, axial fan with rotating impeller
Standard unit
Quantity
6
6
7
8
8
9
11
12
13
13
Maximum total air flow
l/s
28920 28920 33740 38560 38560 43380 53020 57840 62660 62660
Maximum rotation speed
r/s
15,7
15,7
15,7
15,7
15,7
15,7
15,7
15,7
15,7
15,7
Unit + option 15LS
Maximum total air flow
l/s
23580 23580 27510 31440 31440 35370 43230 47160 51090 51090
Maximum rotation speed
r/s
11,7
11,7
11,7
11,7
11,7
11,7
11,7
11,7
11,7
11,7
Water heat exchanger
Flooded multi-pipe type
Water volume
l
58
61
61
66
70
77
79
94
98
119
Max. water-side operating pressure without hydraulic module
kPa
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
Hydraulic module (option)
Pump, Victaulic screen filter, relief valve, water and air drain valve,
pressure sensors, expansion tank (option)
Pump
Centrifugal pump, monocell, 48,3r/s, low or high pressure (as required), single or dual
(as required)
Expansion vessel volume
inch
50
50
50
50
50
80
Max. water-side operating pressure with hydraulic module
mm
400
400
400
400
400
400
Water connections without or with hydraulic module
Victaulic
®
type
Connections
inch
5 or 4
5 or 4
5 or 4
5 or 4
5 or 4
5 or 4
5
6
6
6
External parameter
(5)
mm
114,3 or
141,3
114,3 or
141,3
114,3 or
141,3
114,3 or
141,3
114,3 or
141,3
114,3 or
141,3
141,3
168,3
168,3
168,3
Casing paint
Colour code RAL 7035
(5) Depends of options.
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS
Содержание AquaForce 30XB series
Страница 69: ......