19
4.1 - Physical data 30XB (continued)
30XB-850 to 1700 standard units
30XB
850
900
1000
1100
1200
1300
1400
1500
1550
1700
Sound levels
Standard unit
Sound power
(1)
dB(A)
101
104
102
103
102
104
104
104
104
104
Sound pressure at 10 m
(2)
dB(A)
70
71
69
70
69
71
71
71
71
70
Unit + option 15
(3)
Sound power
(1)
dB(A)
97
99
98
98
98
100
99
99
100
100
Sound pressure at 10 m
(2)
dB(A)
65
66
65
65
65
67
65
65
67
66
Unit + option 15LS
(3)
Sound power
(1)
dB(A)
94
95
94
94
94
99
95
96
96
96
Sound pressure at 10 m
(2)
dB(A)
60
62
65
65
61
65
61
-1
61
61
Unit + option 15LS+
(3)
Sound power
(1)
dB(A)
91
93
92
93
93
97
94
95
93
93
Sound pressure at 10 m
(2)
dB(A)
58
60
59
60
60
66
61
62
60
60
Dimensions
Standard unit
Length
mm
7186
7186
8380
9574
10770 11962
11962 13157
9574/
4798
8380/
8380
Width
mm
2253
2253
2253
2253
2253
2253
2253
2253
2253
2253
Height
mm
2297
2297
2297
2297
2297
2297
2297
2297
2297
2297
Operating weight
(4)
Standard unit
kg
5570
5848
6318
7292
7755
8625
8702
9016
3422/
6714
5957/
5957
Unit + option 15
(3)
kg
5901
6179
6649
7663
8126
8997
9074
9388
3588/
7046
6288/
6288
Unit + option 118A
(3)
kg
6004
6302
6771
-
-
-
-
-
-
-
Unit + option 50
(3)
kg
6430
6805
7272
-
-
-
-
-
-
-
Compressors
06T semi-hermetic screw compressor, 50 r/s
Circuit A
1
1
1
1
1
1
1
1
1
1
Circuit B
1
1
1
1
1
1
1
1
1
1
Circuit C
1
1
Circuit D
1
No. of control stages
Refrigerant for standard unit
(4)
R134a
Circuit A
kg
69
67
71
76
76
110
116
132
85
72
teqCO
2
98,7
95,8
100,8
108,7
108,7
157,3
165,9
188,8
121,6
103,0
Circuit B
kg
65
67
72
108
120
116
124
120
88
63
teqCO
2
93,0
95,8
103,0
154,4
171,6
165,9
177,3
171,6
125,8
90,1
Circuit C
kg
80
72
teqCO
2
114,4
103,0
Circuit D
kg
63
90,1
Oil
Circuit A
l
27,6
27,6
27,6
27,6
27,6
36,0
36,0
36,0
27,6
27,6
Circuit B
l
23,5
27,6
27,6
36,0
36,0
36,0
36,0
36,0
27,6
23,5
Circuit C
l
27,6
27,6
Circuit D
l
23,5
(1) in dB ref=10-12 W, ‘A’ weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). Measured in
accordance with ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20μPa, ‘A’ weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). For information,
calculated from the sound power Lw(A).
(3) Options : 15 = Low noise, 15LS = Very Low noise, 118a = DX freecooling option, 50= Heat recovery.
(4) Values are guidelines only. Refer to the unit name plate.
Eurovent certified