VMU-C
VMU-C Instruction manual
55
alarm configuration page
The following fields need to be configured for each alarm:
Enabled variables: from the drop-down menu you can choose a variable among
the ones included in the list displayed by the system:
Enabled variables
In case of DC energy meter, the available variable list is limited to current, voltage, power
and DC energy.
Set-Point1
: it indicates the alarm activation value (MAXIMUM alarm with Set-
Point1 ≥ Set-Point2; MINIMUM alarm with Set-Point1 < Set-Point2)