VMU-C
VMU-C Instruction manual
54
e)
Enable contribution to the virtual main meter
: if no main instrument has been
defined (from the configured instrument list), VMU-C EM will automatically create
a virtual instrument (one for AC energy and one for DC energy). It will represent
the sum of all the real instrument having this option enabled.
f)
Notes
: notes field.
g)
Baud rate
(bps): specify the communication rate (9600, 19200, 38400 or 115200)
previously set on the instrument.
h)
Data bits
: specify the data format used by the instrument (7 or 8 bits).
i)
Parity
: specify the communication parity type (no parity, even parity, odd parity); it
shall match the values set on the instrument.
j)
Stop bits
: specify the number of stop bits (1 or 2 bits); it shall match the values
set on the instrument.
Pressing the “Save” button will add the energy meter to the list
Note
:
the “Description” field box can take on 3 different colours, having three different
meanings:
-
GREY :
configuration OK and serial communication enabled
-
YELLOW:
configuration OK but serial communication not enabled.
-
RED
:
error in configuration data. Communication with the relevant module will
be impossible.
Click on the “Add” button again to add other energy meters.
3.2.5.2
CONFIGURING SET-POINTS
Press the “Configure Set-Points” button to access the alarm configuration page.
Button granting access to the alarm configuration page
It grants access to the configuration page allowing to configure up to 8 different alarms
for each instrument.
Содержание VMU-C EM
Страница 1: ...VMU C EM Web Server system for energy monitoring Instruction manual Version A6...
Страница 33: ...VMU C VMU C Instruction manual 33 Commands Change of parameters on Eos Array...
Страница 104: ...VMU C VMU C Instruction manual 104...
Страница 108: ...VMU C VMU C Instruction manual 108...
Страница 116: ...VMU C VMU C Instruction manual 116...