The parameters involved are shown below.
Par.
Description
Def
Min
Max
UOM
tLi
Light on with door open
120
0
240
min
A4
Light management
0
Door light button
1
Light button
0
0
1
-
Note:
if the controller is OFF, the light output is controlled only by
the light button. If the controller is ON, the light is controlled by
door light button or light button only, according to the setting
of parameter A4.
Door light button
If A4 = 1, the light is switched on/off only by the light button. The door
status, open or closed, is ignored. If A4 = 0, when the cold room door
is open, the light is always on. When the door is closed, the light can
be switched on or off using the light button. Once on, the light will
automatically switch off after the time set for Li.
LIGHT MANAGEMENT BY DOOR SWITCH AND LIGHT BUTTON
Light_K
Door_sw
Li
t
A4=0
tLi
tLi
OFF
ON
OFF
ON
CL
OP
Fig. 7.m
Key
Light_k
Light button
Li
Light
Door_sw
Door switch
tLi
Light off delay
t
time
7.3 Ultra EVD EVO module commissioning
EVD EVO driver confi guration from UltraCella
Connect UltraCella to the EVD module via serial, as shown in the wiring
diagram in Figure 7.c, and refer to the following parameter table for
confi guration of the EVD EVO driver. The module will become active
when enabled by UltraCella, setting P1 = 1.
If connected via serial, the driver parameters can be displayed only (not
modifi ed) by the local EVD EVO display. Once the driver has been enabled
(parameter P1=1), its parameter settings will be sent by UltraCella, in
accordance with the parameter table below (only modifi able from
UltraCella); any parameters previously confi gured on the EVD EVO display
will be overwritten.
Par.
Description
Def
Min
Max
UOM
P1
Enable communication with EVD EVO
module
1 = EVD module enabled
1
0
1
-
EVD EVO parameter table
The following parameters relating to the EVD EVO driver can be
confi gured from UltraCella
Category: EVO
Par.
Description
Def
Min
Max
UOM
P1
Enable communication with EVD EVO mod-
ule 0/1=disabled/enabled
0
0
1
-
P1t
Type of probe S1
0 0-5 V rat.
2
4-20 mA remote
1 4-20 mA
3
4-20 mA external
0
0
3
-
P1M
Maximum value of probe S1
12.8
-20
200
bar/psi
P1n
Minimum value of probe S1
-1
-20
200
bar/psi
PVt
Typeof valve
1
Carel exv
1
1
22
-
PH
Type of refrigerant
1
R744
3
1
40
-
PrE
Type of main control
1
cabinet/cold room with remote rack
2
cabinet/cold room with on-board
comp.
3
perturbed cabinet/cold room
4
subcritical CO
2
cabinet/cold room
2
1
4
-
P0
EVD Modbus address
198
1
247
-
P3
Superheat set point
10
-72
324
K
P4
Proportional gain
15
0
800
-
P5 Integral
time
150
0
999
sec
P6 Derivative
time
2
0
800
sec
P7
LowSH: low superheat threshold
3
-72
324
K
P8
LowSH: integral time
600
0
800
sec
P9
LowSH: low superheat alarm delay
600
0
999
sec
PL1
LOP: low evap. temperature threshold
-50
-60
200
°C/°F
PL2
LOP: integral time
600
0
800
sec
PL3
LOP: low evaporation temperature alarm
delay
600
0
999
sec
PM1
MOP: max evap. pressure threshold
50
-60
200
°C/°F
PM2
MOP: integral time
600
0
800
sec
PM3
MOP: max evap. pressure alarm delay
10
0
999
sec
cP1
Initial valve position when control starts
(percentage)
50
0
100
%
Pdd
Post defrost delay (single driver only)
10
0
60
min
PSb
Valve position in standby
0
0
100
steps
PMP
Enable manual positioning
0
0
1
-
PMu
Manual valve position
0
0
999
steps
Pnr
Reset EVD setting 0 -> 1 Reset all EVD EVO
parameters
0
0
1
-
PLt
Stop smooth lines off set
2.0
0.0
10.0
°C/°F
PHS
Maximum smooth lines off set
15.0
0.0
50.0
°C/°F
PSP
Smooth lines proportional coeffi
cient
5.0
0.0
100.0 °C/°F
PSI
Smooth lines integral time
120
0
1200
s
PSd
Smooth lines derivative time
0
0
100
s
PSM
Enable smooth lines (0=NO - 1=YES)
0
0
1
/
Note:
set parameters P1=1, P1M and P1n with the values of the
connected probe, PrE=1, PH=11 (R744)
Содержание Hecu CO2
Страница 2: ......
Страница 4: ...4 ENG Hecu CO2 0300085EN rel 2 2 07 05 2019...
Страница 6: ......
Страница 61: ...61 ENG Hecu CO2 0300085EN rel 2 2 07 05 2019 9 2 Software revision history New version 3 0 012...
Страница 62: ...62 ENG Hecu CO2 0300085EN rel 2 2 07 05 2019 Notes...
Страница 63: ......