52
ENG
Hecu
C
O
2
+0300085EN rel. 2.2 - 07.05.2019
Screen
index
Display
Description
Serious
alarm
Alarm
Delay
Reset
ALB15
High suction pressure
Suction pressure exceeds a threshold set on Cae24
x
Cae25
Auto
ALB16
Low suction pressure
Suction pressure below a settable threshold
x
Cae27
Auto
ALB22
Oil sensor level broken
or disconnected
Oil level sensor faulty or not confi gured
correctly (LT only)
The alarm is activated when neither of the two
sensors is active from DI
x
10 s
Auto
ALC01
Alarm 1 compressor 1
Alarm from DI for BLDC compressor set on Cae02 (ge-
neric, overload, high pressure, low pressure, oil)
x
Cae04
Auto/manual
ALC02
Alarm 2 compressor 1
Alarm from DI for BLDC compressor set on Cae05 (ge-
neric, overload, high pressure, low pressure, oil)
x
Cae07
Auto/manual
ALC26
Alarm 1 parallel compressor
Alarm from DI for parallel compressor set on Cbe02
(generic, overload, high pressure, low pressure, oil)
x
Cbe04
Auto/manual
ALC27
Alarm 2 parallel compressor
Alarm from DI for parallel compressor set on Cbe05
(generic, overload, high pressure, low pressure, oil)
x
Cbe07
Auto/manual
ALC51
CO2 level alarm
Refrigerant leakage outside of the circuit
signalled by DI
x
Hc06
Auto
ALC51
Leak detector alarm
Refrigerant leakage in the circuit signalled by DI
x
Hc05
Auto
ALF01
Fan overload
Alarm from DI for one or two fans when fan common
overload is disabled on De05
x
De05
Auto/manual
ALG01
Al_Clock
Alarm due to problem reading controller clock
x
ALG02
Extended memory error
Faulty controller alarm
x
ALG11
High thermostat 1…5 alarms
High temperature (pressure) alarm
for generic function 1 to 5
x
Ffa09-13-17-
21-25
Auto
ALG15
Low thermostat 1…5 alarms
Low temperature (pressure) alarm
for generic function 1 to 5
x
Ffa09-13-17-
21-25
Auto
ALG19
High modulating 1-2 alarms
High temperature (pressure) alarm
for generic modulating function 1 or 2
x
Ffb08-Ffb14
Auto
ALG23
Low modulating 1-2 alarms
Low temperature (pressure) alarm
for generic modulating function 1 or 2
x
Ffb09-Ffb15
Auto
ALG27
Generic 1-2 normal alarms
Generic alarm 1 or 2
x
Ffc07, Ffc09
Auto
ALG28
Generic 1-2 serious alarms
Serious generic alarm 1 or 2
x
Ffc07, Ffc09
Auto
ALT01
Compressor working hours
Operating hours exceeded for the compressor(s)
selected on Cac13
Compressor operating time shown in Cac01
x
Not present
Manual
ALT07
HPV valve alarm
HPV valve alarm from DI settable on Fha04 and HPV
brought to safety position (Fhb10)
x
Not present
Auto
ALT08
RPRV valve alarm
RPRV valve alarm from DI settable on Fha05
and RPRV brought to safety position (Fhb23)
x
Not present
Auto
ALT15
Low superheat alarm
Low SH alarm settable on Cae30
x
Cae30
Auto/manual
ALT19
DSH Low liquid fl owback
SH less than 0 K and DSH at discharge less
than 10 K for a time set on Cae41
x
Cae41
Auto/manual
ALT20
HPV Valve position warning
The HPV valve is at an opening percentage higher than
a certain threshold settable on Fhb27
x
Fhb27
Auto
ALT21
RPRV Valve position warning
The RPRV valve is at an opening percentage higher
than a certain threshold settable on Fhb28
x
Fhb28
Auto
ALT17
HPV set point warning
Gas cooler press. too low/high,
deviation from current set point
P_GC is higher or lower than a diff erential set on Fhb17
in relation to the current set point
x
Fhb17
Auto
ALT18
High receiver pressure alarm
Receiver pressure higher than a settable threshold
(Fhb25)
x
Fhb25
Auto
ALW10
Low superheat warning
The SH value as shown on Aa01 is less than a
threshold set on Cae30
Warning before the alarm is activated, with a delay that
can be set on Cae30
x
Not present
Auto
ALW24
Power plus device offl
ine
BLDC compressor inverter not present
or not connected
x
30-90s
Auto
ALW25
Power+ inverter alarm
Inverter alarm n.xx; ALW25 indicates the type of alarm
generated by the inverter
x
Not present
Auto
ALW26
Compressor start failure
The diff erential between compressor discharge and
suction pressure does not increase by a certain value
in a set period of time. Minimum variation in pressure
diff erence and time period can be set on Cag50
x
Cag50
Auto for 0-9
attempts