40
ENG
Hecu
C
O
2
+0300085EN rel. 2.2 - 07.05.2019
Par
Description
Cat.
Def
Min
Max UOM
A3
Disable door switch
0=enabled
1=disabled
doL
1
0
1
-
tLi
Light off delay
doL
120
0
240
min
A4
Light management
0 = door light button
1 = light button
doL
0
0
1
-
Tab. 7.j
H0: Serial address
Parameter H0 indicates the UltraCella serial address.
Par.
Description
Def
Min
Max
UOM
H0
Serial address
199
0
199
-
Tab. 7.k
The addresses must obey the following logic:
Device
Address
UltraCella 1
11
UltraCella 2
12
UltraCella 3
13
UltraCella 4
14
UltraCella 5
15
While the other parameters that select the protocol are:
•
H7 = 0 Carel protocol
•
H7 = 1 Modbus protocol
H7 must be = 1, while the other parameters retain the default settings,
and are:
Par.
Description
Def
Min
Max UOM
H10
BMS baud rate bit/s
0
1200
5
38400
1
2400
6
57600
2
4800
7
76800
3
9600
8
115200
4
19200
9
375000
4
0
9
-
H11
Number of BMS stop bits
1
1 stop bit
2
2 stop bit
2
1
2
-
H12
BMS parity
0
none
1
odd
2
even
0
0
2
-
Note:
To make the change active, the unit must be switched off and
on again.
C
old room temperature control
Cold room temperature is managed by modulating the electronic
expansion valve.
Probe confi guration
The UltraCella controllers have a maximum of fi ve analogue inputs, three
of which can be confi gured as temperature probes (NTC probes, high
temperature NTC probes, PT1000), the fourth as a temperature probe
or 0-10 V input, the fi fth can be confi gured as a 4-20 mA or 0-5 Vrat input.
Analogue inputs
Type
B1
B2
B3
NTC10 kΩ at 25°C, range -50T90°C,
NTC extended range, NTC50 kΩ at 25°C, range 0T150°C;
PT1000, 1000 Ω at 0°C, range -50T90°C
B4
NTC10 kΩ at 25°C, range -50T90°C,
NTC extended range, NTC50 kΩ at 25°C, range 0T150°C
0 to 10 V
B5
4 to 20 mA
0 to 5 Vrat
0.5 to 4.5 Vrat
Tab. 7.l
The parameter settings are listed below.
Par.
Description
Def
Min
Max
UOM
/P
Type B1…B3
0 = NTC Standard Range -50T90°C
1 = NTC Enhanced Range 0T150°C
2 = PT1000
0
0
2
-
/P4
Type B4
0 = NTC Standard Range -50T90°C
1 = NTC Enhanced Range 0T150°C
2 = 0 to 10 V
0
0
2
-
/P5
Type B5
0 = 4 to 20 mA
1 = 0 to 5 Vrat
2= 0.5 to 4.5 Vrat
0
0
2
-
Assign functions of probes
B1
,
B
2,
B3
,
B4
,
B
5
Inside the cold room, the controller can use the following probes:
•
outlet:
•
intake;
•
defrost, placed on the evaporator, preferably where ice remains the
longest;
Probe B1 is confi gured as an ambient temperature probe and its function
cannot be changed.
Par.
Description
Def
Min
Max
UOM
/A2
B2 confi guration
0
Absent
1
Defrost probe 1 (Sd1)
2
Intake probe (Sr)
3
Generic temperature probe 2
1
0
3
-
/A3
B3 confi guration
0
Absent
1
Defrost probe 2 (Sd2)
2
Cond. probe (Sc)
3
Defrost probe 1 (Sd1)
4
Ambient probe (SA)
5
Generic temperature probe 3
0
0
5
-
/A4
B4 confi guration
0
Absent
1
Ambient temperature probe (SA)
2
Humidity probe
3
Generic temperature probe 4
4
Generic humidity probe 4
0
0
4
-
/A5
B5 confi guration
0
Absent
1
Humidity probe
2
Generic temperature probe 5
3
Generic humidity probe 5
4
Generic pressure probe 5
5
Condensing pressure probe (Scp)
0
0
5
-
For probe B4, if confi gured as a 0 to 10 V input (/P4 = 2) and for probe
B5, the logical values to be used by the controller corresponding to the
physical full scale readings can be assigned.
Par.
Description
Def
Min
Max
UOM
/4L
Minimum value of probe 4 (0 to 10 V input
only)
0
-50.0
/4H
-
/4H
Maximum value of probe 4 (0 to 10 V input
only)
100.0
/4L
200.0
-
/5L
Minimum value of probe 5
0
-50.0
/5H
-
/5H
Maximum value of probe 5
100.0
/5L
999
-
Example:
if a pressure sensor with 4 to 20 mA output is connected to
input B5 with the range -1 to 9.3 bars, set
- /5L = -1,0
- /5H = 9,3
In this case, when the probe reads 12 mA, the value associated with the
reading of B5 will be 4.1 (mid scale).