14
ENG
Hecu
C
O
2
+0300085EN rel. 2.2 - 07.05.2019
2.5 Unipolar E2V valves for R744
A
ØE Out
ØF
O
ut
ØE In
ØF
In
B
C
D
G
43.0
G
44.0
Ø 16
Ø 39
Valve type
A
B
C
D
E
F
G
E2V**CS1C*
125.8mm (4.95 inch)
82.3 mm (3.24inch)
52.3 mm (2.06 inch)
53.3 mm (2.10 inch)
ID 13/OD 18 mm
(in 0.51 out 0.71 inch)
ID 13/OD 18 mm
(in 0.51 out 0.71 inch)
10 mm (0.39 inch)
CAREL E2V-C operating specifi cations
CAREL E2V-U stator
Compatibility
R22, R134a, R404A, R407C,R410A, R744, R507A, R417A
Reference technical document
+050001440
Maximum working
pressure (MWP)
up to 140 barg (2030 PSIg)
Power supply voltage
12 V
Maximum operating
pressure diff erential
(MOPD)
up to 120 bars (1740 PSI)
for E2V24CS0** and E2V24CS1** 85 bars (1233 PSI)
Drive frequency
50 Hz
PED
Gr. 2, art. 3, par. 3
Phase resistance (25 °C)
40 Ohms ± 10%
Refrigerant temperature -40T70 °C (-40T158 °F)
Ingress protection
IP67
Room temperature
-30T70 °C (-22T158 °F)
Connections
6 pin, cable length: 2 m
Contact CAREL for diff erent operating conditions or alternative refrigerants.
Complete closing / control steps
500 / 480
Tab. 2.o
2.6 Pressure probes (SPKT00**8C0)
C
u
sc
i
ta
ou
t
B
a
lim
e
n
ta
zion
e
s
upply
A
non u
t
ilizz
at
o
no
t
u
se
d
Fig. 2.a
Description of codes and models
Part number
Pressure psi
Pressure bars
Mod.
over
range
Burst
pressure
IP
(1)
4 mA 20 mA
4 mA 20 mA
psi
bar psi
bar
SPKT00D8C0
0
2175
0
150
Male
4360 300 7680 530 IP67
SPKT00H8C0
0
1740
0
120
Male
4360 300 7680 530 IP67
Note: (1): with connector plugged in; all sensors are sealed gauge
Technical specifi cations
reference technical document
+050000596
power supply
8-28 Vdc, ±20%
output
4 to 20 mA
mechanical fi tting
¼” male gas (with circular gasket, resistant to
water and oil)
operating temp.
-40T100°C
storage temp.
-20T100°C
fl uid temp. (average)
-20T100°C
linearity
± 1% FS (0 to 50 °C) temperature compensated
± 2% FS (0 to 80 °C); ± 4% FS (-40 to 100 ° C)
ingress protection
IP67 with connector plugged in
shock
20 g* sinusoidal, 11 msec
vibrations
5 to 2000 Hz / 10 g /, X/Y/Z axes / 20 g sen 11
ms
environmental poll. level
normal
insulation
at 50 V ≥ 10 MΩ
response time
(0 to 99%) < 10 msec
EMC
EN 61000-6-1 - 4 / EN 61326-2-3
electrical connections
Packard Plug
tightening force
12-16 Nm
Compatible with all types of refrigerant
Note:
FS = MAX output - MIN output
2.7 Temperature
probes
Models
NTC***HP00
NTC***HT41
NTC***HF01
Reference technical document
+030220655
+030220655
+030220655
Operating range
-50T105 °C in air / -50T50 °C in fl uid
0T150 °C in air
-50T105 °C
Connections
Stripped wire terminals, dimensions: 5±1
mm
Stripped wire terminals, dimensions:
6±1mm
Stripped wire terminals, dimensions:
6±1mm
Sensor
NTC 10 kΩ ±1% at 25 °C Beta 3435
NTC 50 kΩ ±1% at 25 °C Beta 3977
R(25 °C)= 10 kOhm 1%; Beta 3435
Dissipation factor (in air)
approx. 3 mW/°C
approx. 3 mW
3 mW
Thermal constant over time (in air)
approx. 25 s
approx. 30 s
approx. 50 s
Sensor ingress protection
IP67
IP55
IP67
Sensor housing
Polyolefi n
High temperature polyester dim. 20x5 mm Thermoplastic with fi xing tie
Class of protection against electric shock
Basic insulation for 250 Vac
Basic insulation for 250 Vac
Basic insulation for 250 Vac
Heat and fi re resistance cat.
Flame retardant
In accordance with CEI 20-35
UL/HB cable
•
inside showcase temperature
•
discharge temperature
•
evaporation temperature
•
gas cooler outlet temperature