38
ENG
Hecu
C
O
2
+0300085EN rel. 2.2 - 07.05.2019
In: Type of unit
This parameter In assigns the function of Master or Slave to the controller.
Hecu CO2 only accepts MPXPRO master controllers, therefore this
parameter must always be set to “1”.
Par.
Description
Def
Min
Max
UOM
In
Type of unit: 0 = Slave; 1 = Master
0
0
1
-
Tab. 7.a
Sn: Number of slaves in the local network
This parameter tells the Master controller how many Slave controllers it
needs to manage in the local network. Hecu CO2 only accepts MPXPRO
master controllers, therefore this parameter must always be set to “0”.
Par.
Description
Def
Min
Max
UOM
Sn
Number of slaves in the local network
0 = no Slaves
0
0
5
-
Tab. 7.b
H0: Serial or Master Slave network address
Parameter H0 indicates the MPXPRO serial address.
Par.
Description
Def
Min
Max
UOM
H0
Serial or Master Slave network address
199
0
199
-
Tab. 7.i
The addresses must obey the following logic:
Device
Address
MPXPRO 1
11
MPXPRO 2
12
MPXPRO 3
13
MPXPRO 4
14
MPXPRO 5
15
End of procedure
Press Prg/mute for 5 s to exit the guided commissioning procedure.
7.2 Ultracell
confi guration
(SW version ≥ 2.0)
G
eneral connection diagram
G
G0
VBA
T
CO
M
A
NO
A
1
3
2
4
GND
Tx/Rx
DI1
S4
S3
S2
S1
GND
DI2
VREF
2 AT
24 Vac
25 VA
shield
NTC
ratiometric pressure
transducer
S
CAREL
ExV
giallo
/yellow
bianco/
white
verde/
green
marrone/
brown
24 Vac
R6
R5
R4
R3
R2
R1
230 V
20 A max
EN60730-1
UL 873
250 V
R5 - R6
12 (10) A
12 A res. 2HP
12FLA 72 LRA
CAREL NTC, PT1000
CAREL NTC, PT1000
CAREL NTC, PT1000
CAREL NTC, analog input 0 to 10 Vdc
B5 analog input
(4 to 20 mA)
OUT
M
+V
0 to 5 Vdc
DI1
(**)
Door switch
B3
B2
B1
48 47 46 45 44 43
49 50 51 52 53 54
VL
GND
GND
Rx/T
x+
Rx/T
x
-
GND
Rx/T
x+
Rx/T
x
-
GND
Rx/T
x+
Rx/T
x
-
GND
Y1
B4
B5
DI1
DI2
DI3
GND
5 VREF
+ Vdc
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
analog output (0 to 10 Vdc, PWM)
EN60730-1
UL 873
250 V
R3 - R4
10 A res.
5 (3) A
10 A res. 5FLA
18 LRA
EN60730-1
UL 873
250 V
R1 - R2
8 (4) A N.O.
8 A res. 2FLA
12 LRA
DEF
FAN
LIGHT
EVD Module
cod. WM00ENNI00
UltraCella Control
30
29
28
27
26
25
21
20
19
24
23
22
34
35
36
37
38
39
40
41
42
33
32
31
GND
FieldBus
Supervisor
RS485
Shield
BMS
Fig. 7.b
Once the wiring has been completed, simply follow the wizard that is
displayed when the Ultracella devices are switched on for the fi rst time.
Details of this procedure are shown below; for further information see the
UltraCella 0300083EN.
Important:
in order to confi gure the entire system, fi rst check that
the cold rooms are equipped with UltraCella controllers and the
corresponding EEV electronic expansion valve module.