background image

26

ENG

Hecu 

C

O

2

 +0300085EN rel. 2.2 - 07.05.2019

With propor integral control, the integral time is summed to 
the eff ect of proportional control, giving a null control error in steady 
operation. This type of control is illustrated in the following fi gure:

Regulation

variable

P+I

P

Setpoint

time

Fig. 6.g

The integral action depends on time and the deviation from the set point. 
The integral time represents how fast integral control is implemented:

• 

Low values bring fast actions yet more instability

• 

High values bring slower actions and more stability

The values should not be set too low, to avoid system instability. 

Two types of control can be set, in loop 
C

ompressors 

Æ

 Control 

Æ

 screen Cab01

• 

Fixed set point 

• 

Floating set point 

Floating set point 

This software function is available by exploiting serial communication 
with the evaporators. Serial communication allows information to be 
exchanged in real time between the main Hecu CO2 controller and the 
MPXPRO devices. 

Note

: the MPXPRO controllers installed on the evaporators 

implement the Smooth Lines function (see MPXPRO 0300055). 
This function signifi cantly reduces the number of ON-OFF cycles in 
traditional control by modulating the evaporator temperature using an 
electronic expansion valve and adapting the superheat set point using 
appropriate PI control based on the eff ective control temperature.

This function can be enabled and confi gured manually or automatically. 

• 

The automatic procedure involves the Fast Commissioning operation 
described in chapter 7, which automatically confi gures the control 
parameters on both the condensing unit and the evaporators, using 
the default values optimised by CAREL, yet amply modifi able.

• 

To confi gure the function manually, make sure that there is a serial 
connection with the MPXPRO controllers on the evaporators, and 
choose the type of control on 

screen Cab01

. The Smooth Lines 

function will then need to be confi gured on the MPXPRO controllers, 
as described in the next chapter.

The unit fl oating suction pressure set point can vary between a settable 
minimum and maximum value. The minimum and maximum limits for 
the fl oating set point are shown on 

screen Cab04

, in line with the limits 

set on 

screen Cab02.

 

Hecu CO2 uses an advanced algorithm to adapt the condensing unit 
suction pressure set point based on the request from each evaporator, 
then weighing it according to evaporator capacity. Signifi cant variations 
in request due to certain evaporator operating states, such as defrost, are 
managed by Hecu, maintaining fi ne, stable control.
 

Min Set point

energy efficiency

Max Set point

time

Suction

pressure

Fig. 6.h

The fl oating set point will then be managed using propor integral 
control, the parameters of which can be set on 

screen Cab14

Pumpdown

The compressor OFF function by pumpdown can be enabled on screen 
Cag03. This function keeps the compressor on until the pumpdown 
pressure threshold is reached, within the maximum time set on the same 
screen.

Low ambient (outside) temperature prevention:

This function prevents the unit from stopping due to low outside 
temperatures.
The function can be activated if all of the following conditions are true:

1. 

Enabling selected

2. 

The evaporator request is greater than 0% (MPXPRO or ULTRACELLA 
connected) or "Enable compressor from DI" is ACTIVE or the 
diff erential pressure threshold (Prec - Psuc) is less than the set value 
(default 2 bars).

3. 

The outside temperature is less than the value set (default -18°C)

4. 

The compressor request is = 0% and the compressor speed is = 0 for 
longer than the set time (default 30 minutes)

The settings are made on the following screen

When the function is activated:

1. 

The compressor set point is decreased by a settable value (default 8 
bars) within the time set on the same screen

Содержание Hecu CO2

Страница 1: ...I n t e g r a t e d C o n t r o l S o l u t i o n s E n e r g y S a v i n g s NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT High efficiency condensing unit CO2 OEM user manual...

Страница 2: ......

Страница 3: ...use corrosive chemicals solvents or aggressive detergents to clean the device do not use the product for applications other than those speci ed in the technical manual All of the above suggestions lik...

Страница 4: ...4 ENG Hecu CO2 0300085EN rel 2 2 07 05 2019...

Страница 5: ...missioning procedure 21 6 FUNCTIONS 22 6 1 Unit ON OFF 22 6 2 BLDC compressor 22 6 3 Compressor control 25 6 4 Compressor management on LT units DSS and independent 27 6 5 Fans 28 6 6 Oil management 2...

Страница 6: ......

Страница 7: ...80TS0C0 Hecu CO2 controller 24Vac RTC 2 unipolar eev connector kit no BMS FLSMTDMCUTU A ECU80TS0D0 Hecu CO2 controller 24Vac RTC 2 unipolar EEV connector kit no BMS with plastic cover FLSMTDMCUTU A PS...

Страница 8: ...nd 4 x 4 to 20 mA probes Electrical and mechanical specifications of the controller Power supply 230 Vac 10 15 UP2A 24 Vac 10 15 50 60 Hz 28 to 36 Vdc 10 15 UP2B Maximum power input 25 VA Insulation b...

Страница 9: ...resolution 0 1 Hz Inputs 1 motor protection input PTC temp or volt age free contact maximum current 10 mA maximum length 25 m Outputs 1 relay programmable output voltage free contact 240 Vac 1 A Seri...

Страница 10: ...e output voltage free con tact 240 Vac 1 A Serial input RS485 Modbus protocol max baud rate 19200 bit s 24 Vdc aux power supply Double insulation 10 precision 50 mA max Maximum length 100 m shielded c...

Страница 11: ...z unless otherwise speci ed PSD10102BA Rated input current at 230 V 19 2 to 16 A Fuse or type B circuit breaker 25 A Power cable size 4 mm2 Rated output current 12 A Rated output power at 230 V 3 8 kW...

Страница 12: ...C2 GND GND 0 V RS485 ModBus connection three pin plug in connector Tx Rx Tx Rx A STO safety digital input 2 pin plug in connector B E PE earth screw F LEDS POWER green drive powered RUN green drive ru...

Страница 13: ...61800 3 ed 2 0 Adjustable speed electrical power drive systems EMC requirements including speci c test methods EN61000 3 2 Electromagnetic compatibility EMC Part 3 2 Limits Limits for harmonic current...

Страница 14: ...50000596 power supply 8 28 Vdc 20 output 4 to 20 mA mechanical tting male gas with circular gasket resistant to water and oil operating temp 40T100 C storage temp 20T100 C uid temp average 20T100 C li...

Страница 15: ...0 Hz 10 15 for ECU80 24 Vac 10 15 50 60 Hz 28 to 36 Vdc 10 15 to power MPXPRO Ultracella to HECU controller L N Fuse or High press switch MCB U V W L PE K N DC DC 3 4 5 6 7 PTC Klixon Inverter 12A Inv...

Страница 16: ...uction temperature PSUC Suction pressure TDIS Discharge temperature Tout GC Gas cooler temperature PGC Gas cooler pressure PREC Receiver pressure 2 Low temperature configuration The con guration de ne...

Страница 17: ...ddresses 1 and 3 the corresponding dipswitches are set to 0 and 2 which when added to the basic address 1 will give the nal addresses 1 and 3 see the paragraph Network address on page 13 C1 C2 L1 L L2...

Страница 18: ...and polluting atmospheres e g sulphur and ammonia gases saline mist smoke which may cause corrosion and or oxidation strong magnetic and or radio frequency interference thus avoid installation near t...

Страница 19: ...ain screen The main screen is the screen that the Hecu CO2 software automatically returns to 5 minutes after the last button was pressed An example of a main screen is shown in the gure which highligh...

Страница 20: ...nsers a I O status b Regolation c EEV d Energy save e Alarms f Configuration g Advanced E Evaporators a Stato I O b Configuration c Regulation d EVD driver F Other functions a Oil a I O status b Setti...

Страница 21: ...s whether the connected model of inverter is compatible and if so automatically downloads some typical compressor parameters to the inverter The parameters can also be written manually by selecting Ye...

Страница 22: ...OSHIBA DY67 E2V14CS1C0 E2V18CS1C0 PS200152041 0 0 7 6 3 kW TOSHIBA RY100 E2V18CS1C0 E2V24CS1C0 PS200184041 0 1 0 8 8 kW Tab 6 b 0 no PEC version 1 PEC version Note go to ksa carel com to check the upd...

Страница 23: ...nimum On time a minimum O time and a minimum time between two consecutive starts These parameters can be set on screen Caf35 The logic is described in the following graph min ON time min OFF time min...

Страница 24: ...compressor can start The corresponding parameters are found under Compressors Advanced screen Cag49 When the pressure di erential is below 1 barg 0 5 barg xed value the compressor is ready to start Eq...

Страница 25: ...o at low outside temperatures This function can be activated even without using an external heater but rather exploiting a special function implemented in the inverter that controls the compressor The...

Страница 26: ...he MPXPRO controllers on the evaporators and choose the type of control on screen Cab01 The Smooth Lines function will then need to be con gured on the MPXPRO controllers as described in the next chap...

Страница 27: ...compressor cannot start without a request When DSS1 is enabled the following parameters remain hidden on screen Fib04 Switch on period 180s hidden During this period the parallel compressor request i...

Страница 28: ...g to the following relationship g g 6 5 Fans Hecu CO2 can manage up to two fans with a speed modulation device which may be an inverter or a PWM phase control device In the same way as for the compres...

Страница 29: ...ot drastically lower the condensing pressure at start up Floating condensing pressure set point For the condenser line the oating set point enabled on screen Dd05 is based on the outside temperature T...

Страница 30: ...function The parameters can be con gured from screens Bad14 for assigning the analogue output and Fab15 to enabl e the function standard oil separator EEV valve BLDC compressor V Fig 6 r Oil speed bo...

Страница 31: ...be enabled then on screen Fab15 enable the washing cycles as shown below Then select the digital output on screen Faa68 The DO will be used by third party controllers evaporators to activate cabinet s...

Страница 32: ...opening at pressure P100 If the pressure decreases the opening of the HPV valve remains constant until it returns into the transcritical zone where control resumes as described previously Lower propo...

Страница 33: ...procedures Fhb16 High receiver pressure threshold Maximum receiver pressure allowed Maximum o set to be added to the HPV set point when the receiver pressure exceeds the high pressure threshold Fhb17...

Страница 34: ...epending on system con guration Examples for analogue variables Suction pressure Condensing pressure Saturated suction temperature Saturated condensing temperature Suction temperature Discharge temper...

Страница 35: ...fault con guration can be saved therefore if saving the values another time the new values overwrite the previous ones Important the procedure for resetting the Carel default values involves clearing...

Страница 36: ...S5 DI2 S6 DI3 S7 DI4 GND 5Vdc VL GND DI5 M S N Tx Rx T U I Tx Rx Tx Rx R1 R5 R2 R3 R4 AUX2 Power Supply AC 115 230 V 200 mA max PWM modulating fans 20 mA max totally Trim heater Expansion board 0 to1...

Страница 37: ...tandard Range 50T90 C 4 0 to 5 V ratiometric probe 0 0 4 Tab 7 c Note the NTC L243 PTC PT1000 probes can only be con gured on the full optional models or with EEV driver Fd Assign tGS superheated gas...

Страница 38: ...x DI1 S4 S3 S2 S1 GND DI2 VREF 2 AT 24 Vac 25 VA shield NTC ratiometric pressure transducer S CAREL ExV giallo yellow bianco white verde green marrone brown 24 Vac R6 R5 R4 R3 R2 R1 230 V 20 A max EN6...

Страница 39: ...arameters Modification Password 1234 Fig 7 g 2 To enter Programming mode press Prg and enter the password 1234 SET PRG ESC M E N U H E L P Parameters Categ 1 16 1 Probes 2 Control 3 Compressor Fig 7 h...

Страница 40: ...0 to 5 Vrat 0 5 to 4 5 Vrat Tab 7 l The parameter settings are listed below Par Description Def Min Max UOM P Type B1 B3 0 NTC Standard Range 50T90 C 1 NTC Enhanced Range 0T150 C 2 PT1000 0 0 2 P4 Ty...

Страница 41: ...l alarm active not active 2 Do not select 3 enable defrost not enabled enabled 4 start defrost not active active 5 Door switch active not active 6 Remote ON OFF OFF ON 7 Change set point r4 r5 from sw...

Страница 42: ...gital input does not open before the time dP1 elapses the defrost will terminate by time and alarm Ed1 will be displayed defrost ended by timeout opening the digital input does not start the defrost o...

Страница 43: ...module 1 EVD module enabled 1 0 1 EVD EVO parameter table The following parameters relating to the EVD EVO driver can be con gured from UltraCella Category EVO Par Description Def Min Max UOM P1 Enabl...

Страница 44: ...d automatically in accordance with the type of refrigerant and application selected together with the proportional gain and integral time values required by the controller and already shown in paragra...

Страница 45: ...onal gain from 3 to 30 Increasing the proportional gain K increases valve response speed and is recommended if the system is particularly perturbed or to make superheat control faster If greater than...

Страница 46: ...n the condition is no longer present or the controller is switched o standby When low superheat status is activated any local solenoid valves can be forced closed parameter P10 Par Description Def Min...

Страница 47: ...reset and the signal is shown again Automatic when the alarm condition ceases the alarm is automatically acknowledged the LED comes on steady and the corresponding screen remains displayed until Alar...

Страница 48: ...switch Low suction pressure High condensing pressure Alarms from probe Low suction pressure High suction pressure Low condensing pressure High condensing pressure One possible example for the low pres...

Страница 49: ...e fans on and stopping all the compressors ignoring the times 8 4 Anti liquid return MPX valve alarm For alarms that stop the compressor if the anti liquid return MPX valve function is enabled the eva...

Страница 50: ...4 Receiver pressure probe broken or disconnected Receiver pressure probe faulty or not con gured correctly x Not present Auto ALA46 Vapour injection pressure probe broken or disconnected Vapour inject...

Страница 51: ...ol action Vapour injection disabled Check T_vap_inj probe No action on the parallel compressor Parallel compressor stops for control Check P_suc_par probe No action on the parallel compressor Check T_...

Страница 52: ...ssure alarm for generic modulating function 1 or 2 x Ffb09 Ffb15 Auto ALG27 Generic 1 2 normal alarms Generic alarm 1 or 2 x Ffc07 Ffc09 Auto ALG28 Generic 1 2 serious alarms Serious generic alarm 1 o...

Страница 53: ...or operation presence of liquid refrigerant charge sizing Check evaporator valve operation and status valves blocked incorrect con guration wiring Check MPXPRO UC setting probe operation and positioni...

Страница 54: ...MPXPRO P9 Auto ALW47 60 73 86 99 Store 1 5 Low suction temperature alarm Suction temperature t_gs 1 to 5 below threshold with the risk of liquid returning to the compressor x from MPXPRO P12 Auto ALW...

Страница 55: ...heck t_gs and p_ev probes type wiring installation position probe limits reading compared against mechanical device Check alarm settings Check E2V valve operation correct opening closing check that it...

Страница 56: ...a certain threshold set on Hb04 x Not settable Auto ALP06 Parallel compressor low pressure di erential insu cient lubrication Di erence between parallel compressor suction and discharge pressure too l...

Страница 57: ..._par probe type wiring installation position probe limits reading compared against mechanical device Check alarm threshold setting on screen Hb04 Parallel compressor shutdown Check correct compressor...

Страница 58: ...re detailed information on programming the key see to the pCO Manager manual Using the Smart Key with the pCO PC programmable controllers Switch o the pCO remove any peripherals connected in the pLAN...

Страница 59: ...r integrated into the 1tool programming environment Installing pCOmanager Go to http ksa carel com and in the pCO sistema section select pCO_ manager After accepting the general terms and conditions f...

Страница 60: ...following les applicationName 2CW descriptor of categories access pro les monitoring groups CommissioningLogFileName CSV le used for the commissioning log with the data of the variables logged during...

Страница 61: ...61 ENG Hecu CO2 0300085EN rel 2 2 07 05 2019 9 2 Software revision history New version 3 0 012...

Страница 62: ...62 ENG Hecu CO2 0300085EN rel 2 2 07 05 2019 Notes...

Страница 63: ......

Страница 64: ...L INDUSTRIES Headquarters Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency Hecu CO 2 0300085EN rel 2 2 07 05 2...

Отзывы: