FCP manual
Code +030220391 – rel 1.1 07/11/06
36
10. Specifications and connections
10.1 FCPM082010 electrical specifications
Power supply
230 Vac single-phase. -15% +10% 50/60 Hz
Analogue outputs
1 phase control 0-230 Vac single-phase, 8 A (min 500mA)
Digital outputs
1 phase control function for expansion with auxiliary power devices, MCHRTF*
0-5 V 5 mA max;
Analogue inputs
1 configurable input for
- ratiometric pressure probes 0-5V
- std Carel NTC temp. probes (10k
Ω
@25°C) range of measurement: –50°C +90°C
- std Carel NTC temp. probes (50k
Ω
@25°C) range of measurement: 0°C +120°C
- 0/10V control (Rin: 20 k
Ω
)
1 configurable input for
- ratiometric pressure probes 0-5V
- std Carel NTC temp. probes (10k
Ω
@25°C) range of measurement: –50°C +90°C
- std Carel NTC temp. probes (50k
Ω
@25°C) range of measurement: 0°C +120°C
1 configurable input for
- std Carel NTC temp. probes (10k
Ω
@25°C) range of measurement: –50°C +90°C
- std Carel NTC temp. probes (50k
Ω
@25°C) range of measurement: 0°C +120°C
measurement precision (excluding the probes):
- ratiometric probes: 1%
- 0/10V control: 5% (typical 2%)
- NTC probes 10k
Ω
:
±
1°C [-10/50];
±
2°C [-40/-10 and 50/90]
- NTC probes 50k
Ω
:
±
1°C [30/90];
±
2°C [0/30 and 90/120]
Digital inputs
1 input with voltage free contact
typical voltage 12 V with contact open, typical current 6 mA with contact closed.
Serial outputs
1 standard RS485 two wire connector [NOTE 1]
Carel supervisor and ModBus protocol; baud rate 19200; max length 1 km with shielded cable
Signal lights
Green power LED
Red alarm LED
Yellow serial connection active LED (flashes when receiving valid frame)
Controller settings
4 trimmers for manually setting:
- set point
- differential
- minimum speed
- maximum speed
4 dipswitches:
- select manual setting or configuration by parameters
- select function associated with the digital input
- enable double circuit (probe B2)
- enable Cut-off (or other settable function)
2 jumpers:
- 0/10V input configuration
Terminals and connectors
Power supply and analogue outputs:
Screw terminals for cable cross-section min. 2.5 mm
2
max 4 mm
2
.
Signals:
Spring terminals for cable cross-section max 2.5mm
2
.
4 pin JST connector for programming key
Operating conditions
-20/+50°C, <90% rH non-condensing
Storage conditions
-20/+70°C, <90% rH non-condensing
Index of protection
IP54
Environmental pollution
2
Protection against electric shock
Class I
PTI of the insulating materials
250V
Period of stress across the insulating parts
Long
Type of action -disconnection
1Y
Category of resistance to heat and fire
Category D (UL94 – V0)
Immunity against voltage surges
Category II
Ageing characteristics
60,000 operating hours
No. of automatic operating cycles
100,000
Software class and structure
Class A
Case
Metallic (Al) with plastic cover (ball pressure test 75°C)
Dimensions
140x135x90 mm
Assembly
Metal case fastened to panel or wall mounted using 4 screws dia. 3.5/4 mm
Certification EMC:
EN 61326-1, EN 55014-1, EN 55014-2
Safety:
EN 60730-1
Table 10.a
Note 1:
The FCSER00000 option is required
Содержание FCP/1
Страница 1: ...FCP 1 regulator with microprocessor control User manual...
Страница 2: ...2...
Страница 4: ......
Страница 6: ......