FCP manual
Code +030220391 – rel 1.1 07/11/06
32
ELPL
D10
10
0/1
0
1
Enable long impulse phase control
0=disabled
1=enabled
MOID
D11
11
0/1
0
1
Operating logic of digital input ID1
0=normally closed
1=normally
open
D12 to D14
12 to 14
0
0
1
not used
EOVR
D15
15
0/1
0
1
Enable override output (
NOTE
2) 0=disabled 1=enabled
FDEF
D16
16
0/1
0
1
Reset default values (
NOTE
3) 0=no
action 1=enabled
STID
D17
17
0/1
R
1
input ID1 status
0=open
1=closed
STD1
D18
18
0/1
R
1
dipswitch 1 status
0=Off
1=On
STD2
D19
19
0/1
R
1
dipswitch 2 status
0=Off
1=On
STD3
D20
20
0/1
R
1
dipswitch 3 status
0=Off
1=On
STD4
D21
21
0/1
R
1
dipswitch 4 status
0=Off
1=On
ALRM D22
22
0/1
R 1 alarm
status
0=inactive
1=active
PB1A
D23
23
0/1
R
1
probe B1 fault alarm
0=inactive
1=active
PB2A
D24
24
0/1
R
1
probe B2 fault alarm
0=inactive
1=active
PB3A
D25
25
0/1
R
1
probe B3 fault alarm
0=inactive
1=active
OKHZ
D26
26
0/1
R
1
mains freq. reading
0=no ok
1=ok
STHZ D27 27
0/1
R 1 mains
frequency
0=50Hz
1=60Hz
EEPA
D28
28
0/1
R
1
parameter error alarm
0=inactive
1=active
D29 to D32
29 to 32
0
R
1
not used
Table 7.a
Key:
A = indicates analogue variables
I = indicates integer variables
D = indicates digital variables
R = indicates read only variables (no default values, as these are initialised/updated automatically at power-on)
NOTE
1:
The parameter should be modified via serial connection with care, as this implies the dynamic management of the address by the Master.
NOTE
2:
The override control is disabled at power-on and when serial communication is interrupted for more than 10 seconds.
NOTE
3:
The value is automatically set back to 0 when the function is activated.