Carel FCP/1 Скачать руководство пользователя страница 19

FCP manual 

Code +030220391 – rel 1.1 07/11/06 

19

6.11 Overriding 

the 

output 

The output can forced to the desired value required at any time via serial line, irrespective of the value calculated by the controller. This function is temporary and is 
not saved; it is disabled automatically 10 seconds after the termination of the serial connection. 

 

Associated parameters 

par. Spv 

Modb 

range 

def uom description 

OUTV 

 

I37 

137 

0 to 100 

R/W 

1% 

reading/Override output 

EOVR 

D15 

15 

0/1 

Enable override output 

0=disabled 

1=enabled 

Table 6.b.b

 

6.12  Phase control modes 

By default control is based on short impulses (around 3ms). Alternatively, control can be enabled for long impulses (control  is maintained until the end of the half 
period).  
The displacement of the phase control function can also be changed with reference to the zero-crossing of the mains voltage, so as to adapt it to the cos-fi of the fan. 
The linearisation of the output RMS voltage can also be enabled, rather than use the traditional sinusoidal relationship between phase control and voltage. 

Finally, the instant variation in the output can be limited so as to improve the behaviour of the fan, especially when starting from standstill. 

 

Phase delay @ 100% output 

0%

Voltage(RMS) output

100%

OUTV

100%

ELIN on 

ELIN off 

 

Fig. 6.h 

Associated parameters 

par. Spv Modb  range 

def uom description 

DLPL 

I21 

121 

0 to 100 

10 

1% 

Phase displacement (100% -> 90°) 

STEP 

I24 

124 

0 to 10 

1sec 

Output ramp (minimum time for variation from 0% to 100%) 

ELIN 

D9 

0/1 

Enable output linearisation 

0=disabled 

1=enabled 

ELPL 

D10 

10 

0/1 

Enable long impulse phase control 

0=disabled 

1=enabled 

Table 6.b.c

 

6.13  Automatic adaptation to the mains frequency 

At power-on the mains frequency is measured so as to adapt operation to 50Hz or 60Hz 
The status of the mains frequency reading is accessible via serial line. 

 

par. Spv Modb  range 

def uom description 

OKHZ 

D26 

26 

0/1 

mains frequency reading status 

0=not ok 

1=ok 

STHZ D27  27 

0/1 

mains 

frequency 

0=50Hz 

1=60Hz 

Table 6.b.d

 

6.14  Alarm situations and alarm management 

Alarm status is activated in the event of: 

- activation of the thermal protector (or in any case, the opening of the contact connected to the digital input configured as the alarm input); 
- fault on probes B1 or B2; 
- error reading/writing the parameters saved in non-volatile memory (EEPROM). 

The alarm status is signalled by the red LED, depending on the causes, in order of priority: 

on steady   

parameter alarm 

1 impulse   

probe alarm 

2 impulses  

digital input open alarm 

In the event of more than one alarm at the same time, the signal with the highest priority is shown.  

Warning: if digital input ID1 is set as normally open, the alarm is active when ID1 is closed. 
The probe fault alarm is generated if the probe is disconnected or short-circuited. Only the probes enabled by parameter and/or dipswitch are managed (probe B1 is 
enabled by default, while probe B2 can be enabled by dipswitch).  
In alarm status, the controller output provides one of three possible voltage values, with reference to the mains voltage, which can be set by parameter:   0%;  50%;  
100% (default). 

Normal operation is restored automatically as soon as the alarm situation is resolved. In the event of alarms due to errors when reading/writing the parameters, the 
parameters take the default values. The alarm is reset only when a correct parameter copy operation is performed using the key or the parameters are written from 
the supervisor.  
If the alarm persists, the EEPROM is faulty. 

 

Dipswitch 

Function 

 

 

OFF: 

external alarm (thermal protection activated) 

Dip2 

Select digital input function 

ON: 

set point selection (enable double set point) 

OFF: 

single circuit (probe B1 only) 

Dip3 

Enable two circuits 

ON: 

two circuits (both probes B1 and B2) 

Table 6.b.e 

Associated parameters 

par. Spv  Modb 

range 

def uom 

description 

ALMO 

I11 

111 

0 to 2 

Output in alarm  status 
 

0=0% 
1=50% 
2=100% 

PB1E 

D6 

0/1 

Enable probe B1 

0=disabled 

1=enabled 

PB2E 

D7 

0/1 

Enable probe B2 

0=disabled 

1=enabled 

MOID 

D11 

11 

0/1 

Operating logic of digital input ID1 

0=normally closed 

1=normally open 

 

 

 

 

 

 

 

 

Table 6.b.f

Содержание FCP/1

Страница 1: ...FCP 1 regulator with microprocessor control User manual...

Страница 2: ...2...

Страница 3: ...the plastic parts In any case the product should be used or stored in environments that comply with the temperature and humidity limits specified in the manual Do not attempt to open the device in any...

Страница 4: ......

Страница 5: ...ion 16 6 8 Outside temperature compensation feedforward function 17 6 9 PI control proportional and integral 17 6 10 Slave mode function 18 6 11 Overriding the output 19 6 12 Phase control modes 19 6...

Страница 6: ......

Страница 7: ...e increased considerably allowing maximum operating flexibility Control set point and differential Two set points are available which can be selected externally so as to be able to differentiate the o...

Страница 8: ...e type of load Index of protection The gasket inside and the materials used to make the case guarantee the controller IP54 index of protection Fastening The device is fastened using 4 screws CE mark E...

Страница 9: ...be installed so as to ensure normal cooling according to the flow of air Normally if there are no cooling fans it is installed vertically with the cable outlets downwards The temperature of the surfa...

Страница 10: ...sponding terminals Loosen each screw and insert the cable ends then tighten the screws and slightly tug the cables to check that they are sufficiently tight To tighten the screws do not use automatic...

Страница 11: ...case the meaning of Open and Closed must be reversed If slave mode is enabled the external control signal is 0 10V In this case the controller electrical circuits need to be modified using jumper JA a...

Страница 12: ...by dipswitch Two circuit inactive modifiable by dipswitch Cut off inactive modifiable by dipswitch Input B1 Ratiometric pressure probe Input B2 Ratiometric pressure probe Input B3 NTC temperature prob...

Страница 13: ...ED indicates that problems have occurred refer to the table below at the end of the operation release the button after a few seconds the LED goes OFF remove the key from the controller LED signal Caus...

Страница 14: ...ct 1 reverse Table 6 a c 6 2 Configuring the probes and selecting the range of measurement The values of the set point and differential are always internally expressed as a of the range of measurement...

Страница 15: ...nable two circuits ON two circuits both probes B1 and B2 Table 6 a g Associated parameters par Spv Modb range def uom description PB1E D6 6 0 1 1 1 Enable probe B1 0 disabled 1 enabled PB2E D7 7 0 1 1...

Страница 16: ...quivalent to the full mains voltage when the control output increases until reaching the maximum value set the output is forced to the maximum possible and remains there until the conditions require a...

Страница 17: ...en probe B3 is enabled By default probe B3 is disabled and consequently so is the function Trimmer function MIN Feedforward gain setting 0 to 100 Table 6 a s Associated parameters MIN I8 108 0 to MAX...

Страница 18: ...bits plus sign therefore the value 255 corresponds to 100 6 10 Slave mode function The control algorithm is disabled and the output of the controller is directly proportional to input probe B1 in one...

Страница 19: ...1 ok STHZ D27 27 0 1 R 1 mains frequency 0 50Hz 1 60Hz Table 6 b d 6 14 Alarm situations and alarm management Alarm status is activated in the event of activation of the thermal protector or in any ca...

Страница 20: ...ge 1 to 255 default 1 Parameter used to identify the individual controller so as to make it accessible within the supervision network STP1 set point setpoint1 type and Carel supervisor address integer...

Страница 21: ...utput value of the controller Expressed as a of the mains voltage Only used if configuration by parameter rather than by trimmer is enabled MODE slave mode type and Carel supervisor address integer va...

Страница 22: ...ed value in systems whose inertia cannot be accurately defined in advance and therefore when the control function is hard to calibrate DIFF and INTT Only used if PI control is enabled slave mode is no...

Страница 23: ...90 The output should be forced to 100 and parameter DLPL set accordingly to reach the maximum fan speed For resistive loads cos fi 1 the displacement should be set to zero Warning the parameter must b...

Страница 24: ...d unit of measure 1 range 0 to 100 default Variable used to read the value measured by probe B1 expressed as a of the range of measurement Range of measurement ratiometric pressure probes pressure int...

Страница 25: ...INTT I The value calculated is in any case limited as an absolute value by the AWUP parameter The value read is the actual value used in the algorithm expressed in 8 bits plus sign therefore 255 corre...

Страница 26: ...gister 5 resolution and unit of measure 0 1 C range T1L to 120 0 default 120 0 Parameter used to set the upper limit of the range of measurement for NTC 50k probes corresponding to 100 The controller...

Страница 27: ...enabled The parameter has no meaning if the enabling of the Output saturation function is associated with dipswitch 4 par DIP4 EPIR enable PI control type and Carel supervisor address digital var 5 Mo...

Страница 28: ...mains half period The parameter has no meaning if the selection of the type of phase control is associated with dipswitch 4 par DIP4 MOID operating logic of ID1 type and Carel supervisor address digi...

Страница 29: ...e used to read the position of dipswitch 3 STD3 0 Off STD3 1 On STD4 dipswitch 4 status type and Carel supervisor address digital var read only 21 Modbus address read coil 21 resolution and unit of me...

Страница 30: ...on or short circuit The alarm is only detected if probe B3 is enabled The alarm is not detected if slave mode is selected OKHZ mains frequency reading status type and Carel supervisor address digital...

Страница 31: ...R 1 SET trimmer reading tDIF I32 132 0 to 20 R 1 DIF trimmer reading tMIN I33 133 0 to 100 R 1 MIN trimmer reading tMAX I34 134 0 to 100 R 1 MAX trimmer reading PB1R I35 135 0 to 100 R 1 probe B1 rea...

Страница 32: ...robe B1 fault alarm 0 inactive 1 active PB2A D24 24 0 1 R 1 probe B2 fault alarm 0 inactive 1 active PB3A D25 25 0 1 R 1 probe B3 fault alarm 0 inactive 1 active OKHZ D26 26 0 1 R 1 mains freq reading...

Страница 33: ...e are multiple alarms activated at the same time the first in order shown in the table is signalled The active alarm status forces the output to the value defined by the ALMO parameter The alarm statu...

Страница 34: ...ent integer variables relating to parameters I1 I24 integer status variables I31 I42 analogue variables relating to parameters A1 A5 analogue status variables A11 A13 digital variables relating to par...

Страница 35: ...variables requested 16 Address of the first variable requested between 101 150 and address of the first variable requested number of variables requested 150 EXCEPTION 3 Address of the first variable...

Страница 36: ...te 19200 max length 1 km with shielded cable Signal lights Green power LED Red alarm LED Yellow serial connection active LED flashes when receiving valid frame Controller settings 4 trimmers for manua...

Страница 37: ...stics 60 000 operating hours No of automatic operating cycles 100 000 Software class and structure Class A Case Metallic Al with plastic cover ball pressure test 75 C Dimensions 140x135x90 mm Assembly...

Страница 38: ...0220391 rel 1 1 07 11 06 38 10 4 FCPM082A10 connections 230 V Fig 10 b L N Controller 230 Vac power supply input L1 N Power supply output to 0 to 230 Vac load Y1 GND Control input 10 5 Dimensions and...

Страница 39: ......

Страница 40: ...CAREL S p A Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 http www carel com e mail carel carel com Agenzia Agency Code 030220391 Rel 1 1 07 11 06...