FCP manual
Code +030220391 – rel 1.1 07/11/06
22
SUPT Speed-up
duration
type and Carel supervisor address
integer var. 13
Modbus address
read/write register 113
resolution and unit of measure
1s
range
1
to
5
default
2
Parameter used to set the duration of the Speed-up function.
KFF
feedforward gain
type and Carel supervisor address
integer var. 14
Modbus
address
read/write
register
114
resolution and unit of measure
1%
range
0
to
100
default
50
Parameter used to set the intensity of outside temperature compensation.
Only used if:
- configuration by parameter rather than by trimmer is enabled;
- probe B3 and, as a consequence, the outside temperature compensation function is enabled.
INTT integral
time
type and Carel supervisor address
integer var. 15
Modbus address
read/write register 115
resolution and unit of measure
1min
range
1
to
30
default
10
Parameter used to set the intensity of the integral action in PI control.
Only used if:
- PI control is enabled;
- slave mode is not enabled.
AWUP
integral action limit
type and Carel supervisor address
integer var. 16
Modbus address
read/write register 116
resolution and unit of measure
1%
range
0
to
100
default
50
Parameter used to limit the contribution of the integral action in PI control, with the purpose of avoiding excessive overshoot and delays in the controlled value, in
systems whose inertia cannot be accurately defined in advance and therefore when the control function is hard to calibrate (DIFF and INTT). Only used if:
- PI control is enabled;
- slave mode is not enabled.
PB1M
type of probe B1
type and Carel supervisor address
integer var. 17
Modbus address
read/write register 117
resolution and unit of measure
1
range
0
to
3
default
2
Parameter used to select the type of probe or signal connected to input B1.
PB1M=0 Carel NTC temp. probe 10k
Ω
@ 25°C (range of measurement -50 to 90 °C)
PB1M=1 Carel NTC temp. probe 50k
Ω
@ 25°C (range of measurement 0 to 120 °C)
PB1M=2 0/5 V ratiometric pressure probe
PB1M=3 0/10 V signal
(the position of jumpers JA & JB also needs to be modified)
PB2M
type of probe B2
type and Carel supervisor address
integer var. 18
Modbus address
read/write register 118
resolution and unit of measure
1
range
0
to
2
default
2
Parameter used to select the type of probe or signal connected to input B2.
PB1M=0 Carel NTC temp. probe 10k
Ω
@ 25°C (range of measurement -50 to 90 °C)
PB1M=1 Carel NTC temp. probe 50k
Ω
@ 25°C (range of measurement 0 to 120 °C)
PB1M=2 0/5 V ratiometric pressure probe
PB3M
type of probe B3
type and Carel supervisor address
integer var. 19
Modbus address
read/write register 119
resolution and unit of measure
1
range
0
to
1
default
0
Parameter used to select the type of probe or signal connected to input B3.
PB1M=0 Carel NTC temp. probe 10k
Ω
@ 25°C (range of measurement -50 to 90 °C);
PB1M=1 Carel NTC temp. probe 50k
Ω
@ 25°C (range of measurement 0 to 120 °C).