FCP manual
Code +030220391 – rel 1.1 07/11/06
31
7.1
Summary table of operating parameters
name
Carel spv var
Modbus var
range
def.
User
value
res.
uom
description
MAC
I1
101
141
R
1
Type of unit
REL
I2
102
0 to 255
R
1
Software release
SADR
I3
103
1 to 255
1
1
Serial address (
NOTE
1) CAREL
PROT
.
UP TO
207
STP1
I4
104
0 to 100
50
1%
Set point (Set point1)
STP2
I5
105
0 to 100
50
1%
Set point 2
STPM
I6
106
0 to 100
0
1%
Setpoint1 memory set by trimmer
DIFF
I7
107
0 to 100
10
1%
Differential
MIN
I8
108
0 to MAX
30
1%
Minimum output
MAX
I9
109
MIN to 100
100
1%
Maximum output
MODE
I10
110
0 to 3
0
1
Slave mode
0=standard control;
1=slave mode 1
2=slave mode 2
3=slave mode 3
ALMO
I11
111
0 to 2
2
1
Output in alarm status
0=0%
1=50%
2=100%
COFH
I12
112
2 to 100
2
1%
Cut-off activation hysteresis
SUPT
I13
113
1 to 5
2
1sec
Speed-up duration
KFF
I14
114
0 to 100
50
1%
Feedforward gain
INTT
I15
115
1 to 30
10
1min
Integral time in PI control
AWUP
I16
116
0 to 100
50
1%
Integral action limitation (antiwind-up)
PB1M
I17
117
0 to 3
2
1
Type of probe B1
0 = NTC-10k
Ω
3 = 0/10V
PB2M
I18
118
0 to 2
2
1
Type of probe B2
1 = NTC-50k
Ω
PB3M
I19
119
0 to 1
0
1
Type of probe B3
2 = 0/5V ratiometric
DIP4
I20
120
0 to 8
1
1
Select function associated with dipswitch 4 0=no function
1=Cut-off
2=Speed-up
3=Output saturation
4=Long impulse phase control
5=Reverse mode
6=Slave mode1
7=Slave mode2
8=Slave mode3
DLPL
I21
121
0 to 100
10
1%
Phase displacement (100% -> 90°)
SERM
I22
122
0 to 1
0
1
Serial transmission mode
0= Modbus even parity
1= Modbus no parity
FILT
I23
123
0 to 13
6
1
Probe filter
0= minimum filter
13= maximum filter
STEP
I24
124
0 to 10
1
1sec
Output ramp (minimum time for variation from 0% to 100%)
I25 to I30
125 to 130
0
R
not used
tSET
I31
131
0 to 100
R
1%
SET trimmer reading
tDIF
I32
132
0 to 20
R
1%
DIF trimmer reading
tMIN
I33
133
0 to 100
R
1%
MIN trimmer reading
tMAX
I34
134
0 to 100
R
1%
MAX trimmer reading
PB1R
I35
135
0 to 100
R
1%
probe B1 reading as a % of the range of measurement
PB2R
I36
136
0 to 100
R
1%
probe B2 reading as a % of the range of measurement
OUTV
I37
137
0 to 100
R/W
1%
reading/Override output (
NOTA
1)
ERRR
I38
138
-255 to 255
R
1
control error (255 = 100%)
OUTP
I39
139
-255 to 255
R
1
proportional component (255 = 100%)
OUTI
I40
140
-255 to 255
R
1
integral component (255 = 100%)
OUTM
I41
141
0 to 255
R
1
minimum component (255 = 100%)
OUTR
I42
142
0 to 255
R
1
controller output (255 = 100%)
I43 to I50
143 to 150
0
R
1
not used
TFF
A1
1
0.0 to +100.0
+50.0
0.1°C
Max reference outside temp. for feedforward function
T0L
A2
2
-50.0 to T0H
-10.0
0.1°C
Lower limit of meas. range NTC-10k
Ω
corresponding to 0%
T0H
A3
3
T0L to +90.0
+90.0
0.1°C
Upper limit of meas. range NTC-10k
Ω
corresponding to 100%
T1L
A4
4
0.0 to T1H
+20.0
0.1°C
Lower limit of meas. range NTC-50k
Ω
corresponding to 0%
T1H
A5
5
T1L to +120.0
+120.0
0.1°C
Upper limit of meas. range NTC-50k
Ω
corresponding to 100%
A6 to A10
6 to 10
0
R
1
not used
PB1T
A11
11
-50.0 to +150.0
R
0.1°C
probe B1 temperature reading (temp. probe only)
PB2T
A12
12
-50.0 to +150.0
R
0.1°C
probe B2 temperature reading (temp. probe only)
PB3T
A13
13
-50.0 to +150.0
R
0.1°C
probe B3 temperature reading
A14 to A16
14 to 16
0
R
1
not used
EREV D1
1
0/1
0 1 Direct/Reverse mode
0=direct
1=reverse
ESUP D2
2
0/1
1 1 Speed-up
function
0=disabled
1=enabled
ECOF D3
3
0/1
0 1 Cut-off
function
0=disabled
1=enabled
ESMX D4
4
0/1
0 1 Saturation
function 0=disabled
1=enabled
EPIR
D5
5
0/1
0
1
Enable PI control (Integral)
0=disabled
1=enabled
PB1E D6
6
0/1
1 1 Enable
probe
B1
0=disabled
1=enabled
PB2E D7
7
0/1
1 1 Enable
probe
B2
0=disabled
1=enabled
PB3E D8
8
0/1
0 1 Enable
probe
B3
0=disabled
1=enabled
ELIN
D9
9
0/1
1
1
Enable output linearisation
0=disabled
1=enabled