FCP manual 

Code +030220391 – rel 1.1 07/11/06 

15

Status variables associated with the probes 

par. Spv 

Modb 

range 

def 

uom description 

PB1R 

I35 

135 

0 to 100 

1% 

probe B1 reading as a % of the range of measurement 

PB2R 

I36 

136 

0 to 100 

1% 

probe B2 reading as a % of the range of measurement 

PB1T A11 

11 -50.0 

to 

+150.0 

R 0.1°C probe 

B1 temperature reading (temp. probe only) 

PB2T A12 

12 -50.0 

to 

+150.0 

R 0.1°C probe 

B2 temperature reading (temp. probe only) 

PB3T 

A13 

13 

-50.0 to +150.0 

0.1°C 

probe B3 temperature reading 

PB1A 

D23 

23 

0/1 

probe B1 fault alarm 

0=inactive 

1=active 

PB2A 

D24 

24 

0/1 

probe B2 fault alarm 

0=inactive 

1=active 

PB3A 

D25 

25 

0/1 

probe B3 fault alarm 

0=inactive 

1=active 

Table 6.a.f

 

 

6.3 Two 

circuit 

function 

If this function is enabled, control depends on: 
- the higher of the values read by probes B1 and B2 if Direct mode is set; 
- the lower of the values read by probes B1 and B2 if Reverse mode is set. 

If disabled, control only depends on the value ready by probe B1, and the B2 probe input can remain unused without causing probe alarms. 
The function is enabled by dipswitch, but probe B2 must also be enabled by parameter. 
By default probes B1 and B2 are enabled by parameter, but the function is disabled by dipswitch and only probe B1 is used. Warning: if both probes B1 and B2 are 
disabled, the controller forces the output either to the minimum value or to zero, according to the setting of the Cut-off function. 

 

 

Dipswitch 

Function 

 

 

OFF: 

single circuit (probe B1 only) 

Dip3 

Enable two circuits 

ON: 

two circuits (both probes B1 and B2) 

Table 6.a.g

 

 

Associated parameters 

par. Spv Modb  range 

def  uom description 

PB1E D6  6 

0/1 

Enable 

probe 

B1 

0=disabled 

1=enabled 

PB2E D7  7 

0/1 

Enable 

probe 

B2 

0=disabled 

1=enabled 

Table 6.a.h

 

 

 

6.4 

Double set point function 

This is used to allow two different set points, and switch from one to the other based on an external control signal. The function can be enabled by dipswitch. In this 
case, the digital input is used to select setpoint1 or setpoint2. If set by trimmer, the physical limitation of having just one trimmer to set the set point can be overcome 
using the procedure described in the paragraph “Procedure for setting the double set point by trimmer”. 

 

 

Dipswitch 

Function  

 

 

OFF: 

external alarm (thermal protection activated) 

Dip2 

Select digital input function 

ON: 

set point selection (enable double set point) 

Table 6.a.i

 

 

Configuration 

Status of input ID1 

description 

Open 

Set point selection 2 

ID1=Double set point 
(Dip2 ON) 

Closed 

Set point selection 1 

Table 6.a.l

 

 

Trimmer 

Function 

alternative function 

SET 

Set the set point 
0 -100% 

If the double set point is enabled: 
Set the set point 1 (Dip2 OFF) 
Save set point 1 (Dip2 OFF 

Æ

 ON) 

Set the set point 2 (Dip2 ON) 

Table 6.a.m

 

 
Associated parameters 

par. Spv 

Modb 

range 

def 

uom 

description 

STP1 

I4 

104 

0 to 100 

50 

1% 

Set point (Setpoint1) 

STP2 

I5 

105 

0 to 100 

50 

1% 

Setpoint2 

STPM 

I6 

106 

0 to 100 

1% 

Setpoint1 memory set by trimmer 

MOID 

D11 

11 

0/1 

Operating logic of digital input ID1 

0=normally closed 

1=normally open 

Table 6.a.n 

 

The value of set point1 by trimmer (par. STPM), in addition to the manual procedure, can also be set directly by parameter, as for all the other parameters. 

Содержание FCP/1

Страница 1: ...FCP 1 regulator with microprocessor control User manual...

Страница 2: ...2...

Страница 3: ...the plastic parts In any case the product should be used or stored in environments that comply with the temperature and humidity limits specified in the manual Do not attempt to open the device in any...

Страница 4: ......

Страница 5: ...ion 16 6 8 Outside temperature compensation feedforward function 17 6 9 PI control proportional and integral 17 6 10 Slave mode function 18 6 11 Overriding the output 19 6 12 Phase control modes 19 6...

Страница 6: ......

Страница 7: ...e increased considerably allowing maximum operating flexibility Control set point and differential Two set points are available which can be selected externally so as to be able to differentiate the o...

Страница 8: ...e type of load Index of protection The gasket inside and the materials used to make the case guarantee the controller IP54 index of protection Fastening The device is fastened using 4 screws CE mark E...

Страница 9: ...be installed so as to ensure normal cooling according to the flow of air Normally if there are no cooling fans it is installed vertically with the cable outlets downwards The temperature of the surfa...

Страница 10: ...sponding terminals Loosen each screw and insert the cable ends then tighten the screws and slightly tug the cables to check that they are sufficiently tight To tighten the screws do not use automatic...

Страница 11: ...case the meaning of Open and Closed must be reversed If slave mode is enabled the external control signal is 0 10V In this case the controller electrical circuits need to be modified using jumper JA a...

Страница 12: ...by dipswitch Two circuit inactive modifiable by dipswitch Cut off inactive modifiable by dipswitch Input B1 Ratiometric pressure probe Input B2 Ratiometric pressure probe Input B3 NTC temperature prob...

Страница 13: ...ED indicates that problems have occurred refer to the table below at the end of the operation release the button after a few seconds the LED goes OFF remove the key from the controller LED signal Caus...

Страница 14: ...ct 1 reverse Table 6 a c 6 2 Configuring the probes and selecting the range of measurement The values of the set point and differential are always internally expressed as a of the range of measurement...

Страница 15: ...nable two circuits ON two circuits both probes B1 and B2 Table 6 a g Associated parameters par Spv Modb range def uom description PB1E D6 6 0 1 1 1 Enable probe B1 0 disabled 1 enabled PB2E D7 7 0 1 1...

Страница 16: ...quivalent to the full mains voltage when the control output increases until reaching the maximum value set the output is forced to the maximum possible and remains there until the conditions require a...

Страница 17: ...en probe B3 is enabled By default probe B3 is disabled and consequently so is the function Trimmer function MIN Feedforward gain setting 0 to 100 Table 6 a s Associated parameters MIN I8 108 0 to MAX...

Страница 18: ...bits plus sign therefore the value 255 corresponds to 100 6 10 Slave mode function The control algorithm is disabled and the output of the controller is directly proportional to input probe B1 in one...

Страница 19: ...1 ok STHZ D27 27 0 1 R 1 mains frequency 0 50Hz 1 60Hz Table 6 b d 6 14 Alarm situations and alarm management Alarm status is activated in the event of activation of the thermal protector or in any ca...

Страница 20: ...ge 1 to 255 default 1 Parameter used to identify the individual controller so as to make it accessible within the supervision network STP1 set point setpoint1 type and Carel supervisor address integer...

Страница 21: ...utput value of the controller Expressed as a of the mains voltage Only used if configuration by parameter rather than by trimmer is enabled MODE slave mode type and Carel supervisor address integer va...

Страница 22: ...ed value in systems whose inertia cannot be accurately defined in advance and therefore when the control function is hard to calibrate DIFF and INTT Only used if PI control is enabled slave mode is no...

Страница 23: ...90 The output should be forced to 100 and parameter DLPL set accordingly to reach the maximum fan speed For resistive loads cos fi 1 the displacement should be set to zero Warning the parameter must b...

Страница 24: ...d unit of measure 1 range 0 to 100 default Variable used to read the value measured by probe B1 expressed as a of the range of measurement Range of measurement ratiometric pressure probes pressure int...

Страница 25: ...INTT I The value calculated is in any case limited as an absolute value by the AWUP parameter The value read is the actual value used in the algorithm expressed in 8 bits plus sign therefore 255 corre...

Страница 26: ...gister 5 resolution and unit of measure 0 1 C range T1L to 120 0 default 120 0 Parameter used to set the upper limit of the range of measurement for NTC 50k probes corresponding to 100 The controller...

Страница 27: ...enabled The parameter has no meaning if the enabling of the Output saturation function is associated with dipswitch 4 par DIP4 EPIR enable PI control type and Carel supervisor address digital var 5 Mo...

Страница 28: ...mains half period The parameter has no meaning if the selection of the type of phase control is associated with dipswitch 4 par DIP4 MOID operating logic of ID1 type and Carel supervisor address digi...

Страница 29: ...e used to read the position of dipswitch 3 STD3 0 Off STD3 1 On STD4 dipswitch 4 status type and Carel supervisor address digital var read only 21 Modbus address read coil 21 resolution and unit of me...

Страница 30: ...on or short circuit The alarm is only detected if probe B3 is enabled The alarm is not detected if slave mode is selected OKHZ mains frequency reading status type and Carel supervisor address digital...

Страница 31: ...R 1 SET trimmer reading tDIF I32 132 0 to 20 R 1 DIF trimmer reading tMIN I33 133 0 to 100 R 1 MIN trimmer reading tMAX I34 134 0 to 100 R 1 MAX trimmer reading PB1R I35 135 0 to 100 R 1 probe B1 rea...

Страница 32: ...robe B1 fault alarm 0 inactive 1 active PB2A D24 24 0 1 R 1 probe B2 fault alarm 0 inactive 1 active PB3A D25 25 0 1 R 1 probe B3 fault alarm 0 inactive 1 active OKHZ D26 26 0 1 R 1 mains freq reading...

Страница 33: ...e are multiple alarms activated at the same time the first in order shown in the table is signalled The active alarm status forces the output to the value defined by the ALMO parameter The alarm statu...

Страница 34: ...ent integer variables relating to parameters I1 I24 integer status variables I31 I42 analogue variables relating to parameters A1 A5 analogue status variables A11 A13 digital variables relating to par...

Страница 35: ...variables requested 16 Address of the first variable requested between 101 150 and address of the first variable requested number of variables requested 150 EXCEPTION 3 Address of the first variable...

Страница 36: ...te 19200 max length 1 km with shielded cable Signal lights Green power LED Red alarm LED Yellow serial connection active LED flashes when receiving valid frame Controller settings 4 trimmers for manua...

Страница 37: ...stics 60 000 operating hours No of automatic operating cycles 100 000 Software class and structure Class A Case Metallic Al with plastic cover ball pressure test 75 C Dimensions 140x135x90 mm Assembly...

Страница 38: ...0220391 rel 1 1 07 11 06 38 10 4 FCPM082A10 connections 230 V Fig 10 b L N Controller 230 Vac power supply input L1 N Power supply output to 0 to 230 Vac load Y1 GND Control input 10 5 Dimensions and...

Страница 39: ......

Страница 40: ...CAREL S p A Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 http www carel com e mail carel carel com Agenzia Agency Code 030220391 Rel 1 1 07 11 06...

Отзывы: