FCP manual
Code +030220391 – rel 1.1 07/11/06
27
ESUP enable
Speed-up
type and Carel supervisor address
digital var. 2
Modbus address
read/write coil 2
resolution and unit of measure
1
range
0/1
default
1
Parameter used to enable the Speed-up function:
ESUP=0 disabled
ESUP=1 enabled
The parameter has no meaning if the enabling of the function Speed-up is associated with dipswitch 4 (par. DIP4).
ECOF enable
Cut-off
type and Carel supervisor address
digital var. 3
Modbus address
read/write coil 3
resolution and unit of measure
1
range
0/1
default
0
Parameter used to enable the Cut-off function.
ECOF=0 disabled
ECOF=1 enabled
The parameter has no meaning if the enabling of the Cut-off function is associated with dipswitch 4 (parameter DIP4).
ESMX
enable Output saturation
type and Carel supervisor address
digital var. 4
Modbus address
read/write coil 4
resolution and unit of measure
1
range
0/1
default
0
Parameter used to enable the Output saturation function.
ESMX=0 disabled
ESMX=1 enabled
The parameter has no meaning if the enabling of the Output saturation function is associated with dipswitch 4 (par. DIP4).
EPIR
enable PI control
type and Carel supervisor address
digital var. 5
Modbus address
read/write coil 5
resolution and unit of measure
1
range
0/1
default
0
Parameter used to enable PI control (propor integral).
EPIR=0 disabled;
EPIR=1 enabled.
PB1E
enable probe input B1
type and Carel supervisor address
digital var. 6
Modbus address
read/write coil 6
resolution and unit of measure
1
range
0/1
default
1
Parameter used to enable probe input B1. The reading of the probe and any alarms due to probe faults are only activated if the input is enabled.
PB1E=0 disabled
PB1E=1 enabled
PB2E
enable probe input B2
type and Carel supervisor address
digital var. 7
Modbus address
read/write coil 7
resolution and unit of measure
1
range
0/1
default
1
Parameter used to enable probe input B2. The reading of the probe and any alarms due to probe faults are only activated if the input is enabled.
PB2E=0 disabled
PB2E=1 enabled
Warning: probe input B2 (used for two circuit applications) can only be enabled if the Two circuit function is also enabled (dipswitch 3 ON).