FCP manual
Code +030220391 – rel 1.1 07/11/06
26
T0L
lower limit of meas. range NTC-10k
Ω
type and Carel supervisor address
analogue var. 2
Modbus
address
read/write
register
2
resolution and unit of measure
0.1°C
range
-50.0
to
T0H
default
-10.0
Parameter used to set the lower limit of the range of measurement for NTC-10k
Ω
probes, corresponding to 0%. The controller converts the temperature reading into a
% of the range defined by T0L and T0H. If the actual reading is less than T0L, the controller considers this to be 0%.
T0H
upper limit of meas. range NTC-10k
Ω
type and Carel supervisor address
analogue var. 3
Modbus
address
read/write
register
3
resolution and unit of measure
0.1°C
range
T0L
to
90.0
default
90.0
Parameter used to set the upper limit of the range of measurement for NTC-10k
Ω
probes, corresponding to 100%. The controller converts the temperature reading
into a % of the range defined by T0L and T0H. If the actual reading is greater than T0H, the controller considers this to be 100%.
T1L
lower limit of meas. range NTC-50k
Ω
type and Carel supervisor address
analogue var. 4
Modbus
address
read/write
register
4
resolution and unit of measure
0.1°C
range
0.0
to
T1H
default
20.0
Parameter used to set the lower limit of the range of measurement for NTC-50k
Ω
probes, corresponding to 0%. The controller converts the temperature reading into a
% of the range defined by T1L and T1H.If the actual reading is less than T1L, the controller considers this to be 0%.
T1H
upper limit of meas. range NTC-50k
Ω
type and Carel supervisor address
analogue var. 5
Modbus
address
read/write
register
5
resolution and unit of measure
0.1°C
range
T1L
to
120.0
default
120.0
Parameter used to set the upper limit of the range of measurement for NTC-50k
Ω
probes, corresponding to 100%. The controller converts the temperature reading
into a % of the range defined by T1L and T1H. If the actual reading is greater than T1H, the controller considers this to be 100%.
PB1T
probe B1 reading
type and Carel supervisor address
analogue var. (read only) 11
Modbus
address
read
register
11
resolution and unit of measure
0.1°C
range
-50.0
to
150.0
default
--
Variable used to read the temperature value in °C measured by probe B1. If the probe selected is not a temperature probe, the value read is 0.
PB2T
probe B2 reading
type and Carel supervisor address
analogue var. 12
Modbus
address
read/write
register
12
resolution and unit of measure
0.1°C
range
-50.0
to
150.0
default
--
Variable used to read the temperature value in °C measured by probe B2. If the probe selected is not a temperature probe the value read is 0.
PB3T
probe B3 reading
type and Carel supervisor address
analogue var. 13
Modbus
address
read/write
register
13
resolution and unit of measure
0.1°C
range
-50.0
to
150.0
default
--
Variable used to read the temperature value in °C measured by probe B3.
EREV
enable Reverse mode (Direct/Reverse selection)
type and Carel supervisor address
digital var. 1
Modbus address
read/write coil 1
resolution and unit of measure
1
range
0/1
default
0
Parameter used to select Direct or Reverse mode:
EREV=0 Direct (an increase in the value read by the probes increases the value of the output);
EREV=1 Reverse (an increase in the value read by the probes decreases the value of the output).
The parameter has no meaning if the Direct/Reverse selection is associated with dipswitch 4 (parameter DIP4)