FCP manual
Code +030220391 – rel 1.1 07/11/06
29
STID input
ID1
status
type and Carel supervisor address
digital var. (read only) 17
Modbus address
read coil 17
resolution and unit of measure
1
range
0/1
default
--
Variable used to read the status of digital input ID1.
STID=0 open
STID=1 closed
STD1
dipswitch 1 status
type and Carel supervisor address
digital var. (read only) 18
Modbus address
read coil 18
resolution and unit of measure
1
range
0/1
default
--
Variable used to read the position of dipswitch 1.
STD1=0 Off
STD1=1 On
STD2
dipswitch 2 status
type and Carel supervisor address
digital var. (read only) 19
Modbus address
read coil 19
resolution and unit of measure
1
range
0/1
default
--
Variable used to read the position of dipswitch 2.
STD2=0 Off
STD2=1 On
STD3
dipswitch 3 status
type and Carel supervisor address
digital var. (read only) 20
Modbus address
read coil 20
resolution and unit of measure
1
range
0/1
default
--
Variable used to read the position of dipswitch 3.
STD3=0 Off
STD3=1 On
STD4
dipswitch 4 status
type and Carel supervisor address
digital var. (read only) 21
Modbus address
read coil 21
resolution and unit of measure
1
range
0/1
default
--
Variable used to read the position of dipswitch 4.
STD4=0 Off
STD4=1 On
ALRM alarm
status
type and Carel supervisor address
digital var. (read only) 22
Modbus address
read coil 22
resolution and unit of measure
1
range
0/1
default
--
Variable used to read the status of the alarm.
ALRM=0 inactive
ALRM=1 active
The alarm may be signalled externally, associated with the digital input, or due to a fault on probes B1 or B2.
PB1A
probe B1 alarm status
type and Carel supervisor address
digital var. (read only) 23
Modbus address
read coil 23
resolution and unit of measure
1
range
0/1
default
--
Variable used to read the status of the probe B1 fault alarm.
PB1A=0 inactive
PB1A =1 active
The alarm is activated automatically if the value read by probe B1 is outside of the range of possible values, typically due to disconnection or short-circuit. The alarm is only detected if probe B1 is
enabled. The alarm is not detected if slave mode is selected.