6. Description of the functions
6.1 Control
modes
The following operating modes can be set:
Direct
an increase in the value measured by the probes increases the value of the output;
Reverse an increase in the value measured by the probes decreases the value of the output.
OUT
DIRECT
max
min
setp
100%
100%
diff
OUT
REVERSE
max
min
setp
100%
100%
diff
Fig. 6.a
All the functions and observations applied in Direct mode, are valid symmetrically in Reverse mode. Direct mode is set by default (alternatively the selection can be
associated with dipswitch 4).
The values of the set point, differential, minimum and maximum output can be set by dipswitch or by setting the parameters.
If the minimum output set is greater than the maximum output, the value is limited internally to maximum output.
The value of the differential is internally limited so as to in any case ensure the maximum output value set is reached (for example if SET+DIF > 100%, DIF is limited
to 100%-SET).
Dipswitch
Function
OFF:
setting by parameters
Dip1
Select device setting mode
ON:
setting by trimmer
Table 6.a.a
Trimmer
Function
SET
Set the set point
0 – 100%
DIF
Set the differential
0 – 20%
MIN
Set the minimum output
0 – 100%
MAX
Set the maximum output
0 – 100%
Table 6.a.b
Associated parameters
par. Spv Modb range
def uom description
STP1
I4
104
0 to 100
50
1%
Set point (Setpoint1)
STP2
I5
105
0 to 100
50
1%
Setpoint2
STPM
I6
106
0 to 100
0
1%
Setpoint1 memory set by trimmer
DIFF
I7
107
0 to 100
10
1%
Differential
MIN
I8
108
0 to MAX
30
1%
Minimum output
MAX
I9
109
MIN to 100
100
1%
Maximum output
EREV D1 1
0/1
0
1
Direct/Reverse mode
0=direct
1=reverse
Table 6.a.c
6.2
Configuring the probes and selecting the range of measurement
The values of the set point and differential are always internally expressed as a % of the range of measurement used, so as to be able to manage different types of
probes at the same time. For ratiometric pressure probes, the range of measurement is the rated value of the probe.
For temperature probes, the range of measurement can be set by parameter and can be limited compared to the maximum rated value of the probes used, so as to
improve the resolution of control.
type of NTC probe
maximum range settable by parameter
default range
NTC 10k
Ω
@25°C
-50 to +90 °C
-10 to + 90 °C
NTC 50k
Ω
@25°C
0 to +120 °C
+20 to +120 °C
Table 6.a.d
The default range, for both types of probes, has an interval of 100°C so as to simplify the conversion of the set point and above all the differential into a percentage.
The values measured by the probes are digitally filtered to attenuate any external disturbance. The filter can be set by parameter.
Associated parameters
par. Spv Modb range
def uom
description
PB1M
I17
117
0 to 3
2
1
Type of probe B1
0 = NTC-10k
Ω
3 = 0/10V
PB2M
I18
118
0 to 2
2
1
Type of probe B2
1 = NTC-50k
Ω
PB3M
I19
119
0 to 1
0
1
Type of probe B3
2 = 0/5V ratiometric
FILT
I23
123
0 to 13
6
1
Probe filter
0=minimum filter
13=maximum filter
T0L
A2
2
-50.0 to T0H
-10.0
0.1°C
Lower limit of meas. range NTC-10k
Ω
corresponding to 0%
T0H A3 3
T0L
to
+90.0 +90.0 0.1°C Upper limit of meas. range NTC-10k
Ω
corresponding to 100%
T1L
A4
4
0.0 to T1H
+20.0
0.1°C
Lower limit of meas. range NTC-50k
Ω
corresponding to 0%
T1H
A5
5
T1L to +120.0
+120.0
0.1°C
Upper limit of meas. range NTC-50k
Ω
corresponding to 100%
PB1E
D6
6
0/1
1
1
Enable probe B1
0=disabled
1=enabled
PB2E
D7
7
0/1
1
1
Enable probe B2
0=disabled
1=enabled
PB3E
D8
8
0/1
0
1
Enable probe B3
0=disabled
1=enabled
Table 6.a.e