6.  Description of the functions 

 

6.1 Control 

modes 

The following operating modes can be set: 

Direct 

an increase in the value measured by the probes increases the value of the output; 

Reverse  an increase in the value measured by the probes decreases the value of the output. 

 

OUT 

DIRECT 

max 

min 

setp 

100%

100% 

diff 
 

OUT

REVERSE 

max

min

setp

100% 

100%

diff
 

 

Fig. 6.a 

 

All the functions and observations applied in Direct mode, are valid symmetrically in Reverse mode. Direct mode is set by default (alternatively the selection can be 
associated with dipswitch 4). 
The values of the set point, differential, minimum and maximum output can be set by dipswitch or by setting the parameters.  
If the minimum output set is greater than the maximum output, the value is limited internally to maximum output. 

The value of the differential is internally limited so as to in any case ensure the maximum output value set is reached (for example if SET+DIF > 100%, DIF is limited 
to 100%-SET). 

 

Dipswitch 

Function 

 

 

OFF: 

setting by parameters 

Dip1 

Select device setting mode 

ON: 

setting by trimmer 

Table 6.a.a

 

Trimmer 

Function 

SET 

Set the set point  

0 – 100% 

DIF 

Set the differential 

0 – 20% 

MIN 

Set the minimum output 

0 – 100% 

MAX 

Set the maximum output 

0 – 100% 

Table 6.a.b

 

Associated parameters 

par. Spv Modb  range 

def  uom description 

STP1 

I4 

104 

0 to 100 

50 

1% 

Set point (Setpoint1) 

STP2 

I5 

105 

0 to 100 

50 

1% 

Setpoint2 

STPM 

I6 

106 

0 to 100 

1% 

Setpoint1 memory set by trimmer 

DIFF 

I7 

107 

0 to 100 

10 

1% 

Differential 

MIN 

I8 

108 

0 to MAX 

30 

1% 

Minimum output 

MAX 

I9 

109 

MIN to 100 

100 

1% 

Maximum output 

EREV D1  1 

0/1 

Direct/Reverse mode 

0=direct 

1=reverse 

Table 6.a.c

 

 

6.2 

Configuring the probes and selecting the range of measurement 

The values of the set point and differential are always internally expressed as a % of the range of measurement used, so as to be able to manage different types of 

probes at the same time. For ratiometric pressure probes, the range of measurement is the rated value of the probe.  
For temperature probes, the range of measurement can be set by parameter and can be limited compared to the maximum rated value of the probes used, so as to 
improve the resolution of control. 

 

type of NTC probe 

maximum range settable by parameter 

default range 

NTC 10k

 @25°C 

-50 to +90 °C 

-10 to + 90 °C 

NTC 50k

 @25°C 

0 to +120 °C 

+20 to +120 °C 

Table 6.a.d

 

The default range, for both types of probes, has an interval of 100°C so as to simplify the conversion of the set point and above all the differential into a percentage. 
The values measured by the probes are digitally filtered to attenuate any external disturbance. The filter can be set by parameter. 

 

Associated parameters 

par. Spv Modb  range 

def uom 

description 

PB1M 

I17 

117 

0 to 3 

Type of probe B1 

0 = NTC-10k

Ω

 

3 = 0/10V 

PB2M 

I18 

118 

0 to 2 

Type of probe B2 

1 = NTC-50k

Ω

 

 

PB3M 

I19 

119 

0 to 1 

Type of probe B3 

2 = 0/5V ratiometric 

 

FILT 

I23 

123 

0 to 13 

Probe filter 

0=minimum filter 
13=maximum filter 

 

T0L 

A2 

-50.0 to T0H 

-10.0 

0.1°C 

Lower limit of meas. range NTC-10k

Ω

 corresponding to 0% 

T0H A3  3 

T0L 

to 

+90.0  +90.0  0.1°C  Upper limit of meas. range NTC-10k

Ω

 corresponding to 100% 

T1L 

A4 

0.0 to T1H 

+20.0 

0.1°C 

Lower limit of meas. range NTC-50k

Ω

 corresponding to 0% 

T1H 

A5 

T1L to +120.0 

+120.0 

0.1°C 

Upper limit of meas. range NTC-50k

Ω

 corresponding to 100% 

PB1E 

D6 

0/1 

Enable probe B1 

0=disabled 

1=enabled 

PB2E 

D7 

0/1 

Enable probe B2 

0=disabled 

1=enabled 

PB3E 

D8 

0/1 

Enable probe B3 

0=disabled 

1=enabled 

Table 6.a.e 

Содержание FCP/1

Страница 1: ...FCP 1 regulator with microprocessor control User manual...

Страница 2: ...2...

Страница 3: ...the plastic parts In any case the product should be used or stored in environments that comply with the temperature and humidity limits specified in the manual Do not attempt to open the device in any...

Страница 4: ......

Страница 5: ...ion 16 6 8 Outside temperature compensation feedforward function 17 6 9 PI control proportional and integral 17 6 10 Slave mode function 18 6 11 Overriding the output 19 6 12 Phase control modes 19 6...

Страница 6: ......

Страница 7: ...e increased considerably allowing maximum operating flexibility Control set point and differential Two set points are available which can be selected externally so as to be able to differentiate the o...

Страница 8: ...e type of load Index of protection The gasket inside and the materials used to make the case guarantee the controller IP54 index of protection Fastening The device is fastened using 4 screws CE mark E...

Страница 9: ...be installed so as to ensure normal cooling according to the flow of air Normally if there are no cooling fans it is installed vertically with the cable outlets downwards The temperature of the surfa...

Страница 10: ...sponding terminals Loosen each screw and insert the cable ends then tighten the screws and slightly tug the cables to check that they are sufficiently tight To tighten the screws do not use automatic...

Страница 11: ...case the meaning of Open and Closed must be reversed If slave mode is enabled the external control signal is 0 10V In this case the controller electrical circuits need to be modified using jumper JA a...

Страница 12: ...by dipswitch Two circuit inactive modifiable by dipswitch Cut off inactive modifiable by dipswitch Input B1 Ratiometric pressure probe Input B2 Ratiometric pressure probe Input B3 NTC temperature prob...

Страница 13: ...ED indicates that problems have occurred refer to the table below at the end of the operation release the button after a few seconds the LED goes OFF remove the key from the controller LED signal Caus...

Страница 14: ...ct 1 reverse Table 6 a c 6 2 Configuring the probes and selecting the range of measurement The values of the set point and differential are always internally expressed as a of the range of measurement...

Страница 15: ...nable two circuits ON two circuits both probes B1 and B2 Table 6 a g Associated parameters par Spv Modb range def uom description PB1E D6 6 0 1 1 1 Enable probe B1 0 disabled 1 enabled PB2E D7 7 0 1 1...

Страница 16: ...quivalent to the full mains voltage when the control output increases until reaching the maximum value set the output is forced to the maximum possible and remains there until the conditions require a...

Страница 17: ...en probe B3 is enabled By default probe B3 is disabled and consequently so is the function Trimmer function MIN Feedforward gain setting 0 to 100 Table 6 a s Associated parameters MIN I8 108 0 to MAX...

Страница 18: ...bits plus sign therefore the value 255 corresponds to 100 6 10 Slave mode function The control algorithm is disabled and the output of the controller is directly proportional to input probe B1 in one...

Страница 19: ...1 ok STHZ D27 27 0 1 R 1 mains frequency 0 50Hz 1 60Hz Table 6 b d 6 14 Alarm situations and alarm management Alarm status is activated in the event of activation of the thermal protector or in any ca...

Страница 20: ...ge 1 to 255 default 1 Parameter used to identify the individual controller so as to make it accessible within the supervision network STP1 set point setpoint1 type and Carel supervisor address integer...

Страница 21: ...utput value of the controller Expressed as a of the mains voltage Only used if configuration by parameter rather than by trimmer is enabled MODE slave mode type and Carel supervisor address integer va...

Страница 22: ...ed value in systems whose inertia cannot be accurately defined in advance and therefore when the control function is hard to calibrate DIFF and INTT Only used if PI control is enabled slave mode is no...

Страница 23: ...90 The output should be forced to 100 and parameter DLPL set accordingly to reach the maximum fan speed For resistive loads cos fi 1 the displacement should be set to zero Warning the parameter must b...

Страница 24: ...d unit of measure 1 range 0 to 100 default Variable used to read the value measured by probe B1 expressed as a of the range of measurement Range of measurement ratiometric pressure probes pressure int...

Страница 25: ...INTT I The value calculated is in any case limited as an absolute value by the AWUP parameter The value read is the actual value used in the algorithm expressed in 8 bits plus sign therefore 255 corre...

Страница 26: ...gister 5 resolution and unit of measure 0 1 C range T1L to 120 0 default 120 0 Parameter used to set the upper limit of the range of measurement for NTC 50k probes corresponding to 100 The controller...

Страница 27: ...enabled The parameter has no meaning if the enabling of the Output saturation function is associated with dipswitch 4 par DIP4 EPIR enable PI control type and Carel supervisor address digital var 5 Mo...

Страница 28: ...mains half period The parameter has no meaning if the selection of the type of phase control is associated with dipswitch 4 par DIP4 MOID operating logic of ID1 type and Carel supervisor address digi...

Страница 29: ...e used to read the position of dipswitch 3 STD3 0 Off STD3 1 On STD4 dipswitch 4 status type and Carel supervisor address digital var read only 21 Modbus address read coil 21 resolution and unit of me...

Страница 30: ...on or short circuit The alarm is only detected if probe B3 is enabled The alarm is not detected if slave mode is selected OKHZ mains frequency reading status type and Carel supervisor address digital...

Страница 31: ...R 1 SET trimmer reading tDIF I32 132 0 to 20 R 1 DIF trimmer reading tMIN I33 133 0 to 100 R 1 MIN trimmer reading tMAX I34 134 0 to 100 R 1 MAX trimmer reading PB1R I35 135 0 to 100 R 1 probe B1 rea...

Страница 32: ...robe B1 fault alarm 0 inactive 1 active PB2A D24 24 0 1 R 1 probe B2 fault alarm 0 inactive 1 active PB3A D25 25 0 1 R 1 probe B3 fault alarm 0 inactive 1 active OKHZ D26 26 0 1 R 1 mains freq reading...

Страница 33: ...e are multiple alarms activated at the same time the first in order shown in the table is signalled The active alarm status forces the output to the value defined by the ALMO parameter The alarm statu...

Страница 34: ...ent integer variables relating to parameters I1 I24 integer status variables I31 I42 analogue variables relating to parameters A1 A5 analogue status variables A11 A13 digital variables relating to par...

Страница 35: ...variables requested 16 Address of the first variable requested between 101 150 and address of the first variable requested number of variables requested 150 EXCEPTION 3 Address of the first variable...

Страница 36: ...te 19200 max length 1 km with shielded cable Signal lights Green power LED Red alarm LED Yellow serial connection active LED flashes when receiving valid frame Controller settings 4 trimmers for manua...

Страница 37: ...stics 60 000 operating hours No of automatic operating cycles 100 000 Software class and structure Class A Case Metallic Al with plastic cover ball pressure test 75 C Dimensions 140x135x90 mm Assembly...

Страница 38: ...0220391 rel 1 1 07 11 06 38 10 4 FCPM082A10 connections 230 V Fig 10 b L N Controller 230 Vac power supply input L1 N Power supply output to 0 to 230 Vac load Y1 GND Control input 10 5 Dimensions and...

Страница 39: ......

Страница 40: ...CAREL S p A Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 http www carel com e mail carel carel com Agenzia Agency Code 030220391 Rel 1 1 07 11 06...

Отзывы: