NL240 Wireless Network Link Interface
the IP address of the NL240 in
LoggerNet Setup
in order for
LoggerNet
to communicate through the NL240. For example, if the
NL240 is configured as a CS I/O serial server, in
LoggerNet Setup
,
enter the correct IP address of your NL240 followed by :6783 (e.g.,
192.168.0.3:6783).
6.
If you are unable to communicate with the NL240 via the USB cable,
verify that you have installed the latest drivers for the NL240. These can
be downloaded from our website at
www.campbellsci.com
.
7.
If the NL240 is configured as a CS I/O serial server, verify that any other
SDC device attached to the datalogger is using a different SDC address.
For example, if the NL240 is configured for SDC7, any other device
attached to the datalogger cannot use SDC7.
8.
If communicating over a slow or intermittent connection, it may be
necessary to lower the Maximum Packet Size of the datalogger in
LoggerNet Setup
and/or add Extra Response Time to the PakBus Port in
LoggerNet Setup
.
9.
Reset the NL240 to its default settings.
•
If none of the above steps correct your communication problems, reset
the NL240 to its default settings. This can be done using the
Factory
Defaults
button in
DevConfig
or by using the
Defaults
command in a
telnet session with the NL240.
10. Verify you are running the latest revision of firmware (operating system).
It is possible that an issue affecting your ability to communicate via the
NL240 is resolved in the latest version. The latest firmware version and
its revision history can be found at
www.campbellsci.com/downloads
.
There is no charge for this download. See Appendix
D
,
Sending a New OS
to the NL240
(p. D-1)
, for instructions on downloading the firmware revision
to the NL240.
11. If the above steps do not resolve the issue, please call Campbell Scientific,
for help. Before calling, it would be helpful to do the following:
•
Obtain a detailed description of your network setup including TCP/IP
address, port number, PakBus® settings, and other pertinent
information regarding all of the devices in the NL240’s
communication network.
•
Save a copy of the NL240 settings (in XML format) using
DevConfig
.
•
Save a copy of the NL240 event log. This is low-level code that can
be used by Campbell Scientific’s engineering staff to help
troubleshoot the NL240. To obtain the event log, the NL240 must not
be in Bridge Mode. Telnet into the NL240 using your favorite telnet
program. Once you have logged in, type “eventlog” at the prompt.
Record the date and time that you did this. Copy and paste the output
into a text file.
32
Содержание NL240
Страница 2: ......
Страница 6: ......
Страница 10: ...Table of Contents iv...
Страница 44: ...NL240 Wireless Network Link Interface 34...
Страница 50: ...Appendix B Cables Pinouts LED Function and Jumper B 4...
Страница 68: ...Appendix C NL240 Settings C 18...
Страница 72: ...Appendix E Radio Frequency Emission E 2...
Страница 73: ......