Electro-pneumatic Regulator ER100
Instruction Manual
rev. 2.0
page 7 / 38
2.
INSTALLATION
•
Keep a sufficient space for operation & re-installation, wiring and piping
work around the product.
•
Provide a pneumatic filter just in the pre-stage of the circuit in which
the pneumatic equipment is used.
•
IMPORTANT
. Do never block the exhaust port. Always reserve space
necessary for exhaust air.
•
The rotation mechanism of the D-sub connector is not to be considered
as a flexible joint for moving units (continuous oscillation). Use at either
the top or side position (do not use at an angle in between), and fix the
cable if the cable moves.
(
)
(
)
(×)
•
Do not detach the port seal until piping work is started.
・
If the port seal is removed before piping work, dirt may enter into the
interior from the piping port, thus causing trouble and malfunctions, etc.
•
Sufficiently flush/blow air pipes before connecting to the Electro-
pneumatic regulator Series ER. Check that sealing tape is not caught
when piping.
•
When applying a seal tape, start from a position 2-mm or more away
from the end of the thread portion on the tube, to a direction opposite
to the tip of the tube, and wind the tape around the tube in a direction
reverse to the direction of the thread.
・
If a part of the seal tape is positioned closer to the tip of the tube than
the thread portion, the tape may be threaded into pieces as the tube is
screwed into the joint; they may go into the pneumatic equipment and
cause trouble.
Pilot exhaust air
Main exhaust air
5mm or more
Wall
!
CAUTION
: