Electro-pneumatic Regulator ER100
Instruction Manual
rev. 2.0
page 42 / 38
7. REFERENCE
7.1.
Relationship between parallel type input signal and control
pressure
The parallel type input signal is 10 bit width. The signal ranges from 0 to 1023 when converted into a
decimal.
Input signal = ER set pressure (Bar) / Max. control pressure (Bar) × 1023
Max. control pressure ER104-5: 5 Bar
ER104-9: 9 Bar
Example: In the case of setting 3 Bar to ER104-5xxx.
3
(
Bar
)
/ 5
(
Bar
)
× 1023 = 613,8 614
The inverse operation with “614” is:
5
(
Bar
)
× 614 / 1023
≅
3
(
Bar
)
“614” (decimal) converted into a binary is 1001100110. Turn the input signal on at “1” and turn it off at
“0.” (See the table below.)
7.2.
Relationship between preset memory and input signal
D sub socket pin
No.
12 11 9 8 7 6 4 3 2 1
Cable option
Isolator color
Green
(with
black
line)
White
Red
(with
black
line)
White
(with
black
line)
Pink
Pale
blue
Purple Yellow Orange Brown
Input type
10 bit
MSB
9 bit
8 bit
7 bit
6 bit
5 bit
4 bit
3 bit
2 bit
1 bit
LSB
Binary code
[ 614(decimal) ]
1 0 0 1 1 0 0 1 1 0
Input
signal
ON OFF OFF ON ON OFF OFF ON ON OFF
D-sub socket pin
No.
3 2 1
Cable option
Isolator color
Yellow Orange Brown
Input type
3 bit
2 bit
1 bit
Preset
memory
OFF OFF OFF
P1
OFF OFF ON
P2
OFF ON OFF
P3
OFF ON ON
P4
ON OFF OFF
P5
ON OFF ON
P6
ON ON OFF
P7
Input signal
ON ON ON
P8