32
/ 55
there
is
a
sudden
overcurrent in the power
supply output.
before restarting the power
supply.
4
Precharge
timeout
Internal error caused by a
low voltage in mains.
Check the grid voltage.
5
Overload in
precharge
Internal alarm caused by a
shortcircuit.
Contact Cinergia for technical
support.
6
Overvoltage in
the DC link
The DC link voltage has
exceeded its maximum
value.
Reduce the DC output step
transition time.
Contact Cinergia for technical
support if this alarm persists.
7
Undervoltage in
the DC link
Undervoltage in the DC link
caused by fast output
transient.
Reduce the DC output step
transition time.
Contact Cinergia for technical
support if this alarm persists.
8
Phase
overvoltage
The voltage in the grid is
too high.
Check the grid voltage.
9
Phase
undervoltage
The voltage in the grid is
too low.
Check the grid voltage.
10
DC Overcurrent
The output current has
exceeded the configured
limitation.
Check the output load.
11
Heatsink
overtemperature
Overtemperature in the
heatsink.
Check
enough
space
exists
between the power supply and
the wall.
There is insufficient air flow inside
the power supply. Check that the
fans are working correctly.
11
Sensor offset
Error caused by transducers
malfunction.
Turn off the equipment, wait one
minute, and turn it on again. This
alarm can occur when the power
supply is switched off accidentally
under load.
Otherwise, contact Cinergia for
technical support.