10

EN 

4.4    Advanced options 

4.4.1  Programmable Alarm relay

The Inverter Charger Combi is equipped with one or two (depending 
on model) programmable potential free alarm relays. Standard, this 
relay (or relay 1 on ICC 3000 SI-N/120A model) will be activated when 
the unit shuts down and jumps to an error mode. The alarm relay 
de-activates again when the error has been resolved and the Inverter 
Charger Combi is running in normal operating mode again. 

Relay 2 on the ICC 3000 SI-N/120A model will be activated only after 
the AC supply has become available. In case of battery operation, Relay 
2 will deactivate immediately. This can be used to switch less critical 
AC loads (i.e. electric boiler, aircon) on and off that are allowed to be 
supplied by the mains or generator only.

Using Dashboard software, it is also possible to configure the pro-
grammable relays to perform a different task, like starting a generator 
when the battery voltage has reached a certain low voltage level.  
Both normally closed and normally open contacts of these relays are 
available. For the ICC 1600 SI-N/60A model, the maximum relay contact 
ratings are 30VDC/1A or 60VDC/0.3A. For the ICC 3000 SI-N/120A model, 
the maximum relay contact ratings are 30Vdc/16A or 250Vac/16A.

4.4.2  Trigger input

The trigger input offers a way of externally controlling the behaviour 
of the Inverter Charger Combi. The trigger input can be connected to 
an external switch or a potential free relay contact. By closing this  
external switch or contact, a user programmable “action” will be  
performed. Such an action could for example be to release the  
AC transfer switch, temporarily disable the AC input Power Boost  
feature or force the Inverter Charger Combi to switch to inverter mode. 
All this can be configured. The ICC 1600 model is equipped with one 
trigger input, while the ICC 3000 models is equipped with two trigger 
inputs.

4.5  Load requirements in inverter mode

Before you connect your appliance(s) to the Inverter Charger Combi AC 
output, always check it’s maximum power consumption. Do not 
connect appliances to the AC output requiring more than the nominal 
power rating of the inverter continuously. Unless these appliances are 
switched on only when the AC transfer switch is activated, and power 
is drawn from an external source with a larger capacity than the inverter. 

Some appliances like motors or pumps, draw large inrush currents at 
startup. It is possible that the startup current exceeds the overcurrent 
trip level of the inverter. In this case the output voltage will shortly 
decrease to limit the output current of the inverter. If the overcurrent 
trip level is continuously exceeded, the inverter will shut down and 
automatically restart within 20 seconds. In this case it is advisable to 
disconnect this appliance from the inverter, since it requires too much 
power to be driven by this unit. The Inverter Charger Combi needs to 
be restarted manually when it has shut down due to overloads for four 
times in a row. Note that at higher ambient temperature levels, the 
overload capacity of the Inverter Charger Combi will be reduced.

5. Charger operation 

5.1  Charge programs

All standard selectable charge programs (using DIP switches 4, 5 and 6), 
perform a four stage IUoUoP charging process comprising of a “Bulk”, 
an “Absorption”, a “Float” and a “Pulse” stage. The image below  
visualizes the four stage charging process:

In the Bulk stage, the charger delivers full output current and typically 
returns approximately 80 % of charge back into the battery once the 
absorption voltage is reached. During this stage, the battery empty 
and battery 50 % full indicators will be lit depending on the Bulk  
charge progress. When the absorption voltage has been reached, the 
Absorption stage will be entered and the battery 80 % full indicator 
will be lit. This stage will return the final 20 % of charge to the battery. 
The output voltage is kept at a constant level and the charge current 
decreases as a function of the battery’s state of charge. When the  
charge current has dropped below a certain value or when the  
maximum absorption timer has been expired, the Float stage will be 
entered. The battery full Indicator will be lit and an acoustical message 
will sound, indicating that the battery is full. In this stage the battery 
voltage will be held constant at a safe level for the battery. It will  
maintain the battery in optimal condition for as long as the battery 
remains connected to the activated charger. Connected battery loads 
will be directly powered by the charger up to the charger’s maximum 
output current level. When even more current is drawn, the battery 
must supply this which results in a declining battery voltage. At a  
certain battery voltage level, the charger jumps back to the Bulk stage 
and will finalize a complete charging process again, once the battery 
load consumption has dropped below the charger’s maximum output 
current level.

The fourth stage called “Pulse”, will perform a short refresh charge of 
approximately 1 hour each 7 days while the charger operates in the 
Float stage. 

Содержание MT 81660

Страница 1: ...charger combi ICC Wechselrichter Ladeger t Kombination ICC combinaison convertisseur chargeur MT ICC 1600 SI N 60 A Nr MT 81660 MT ICC 3000 SI N 120 A Nr MT 83120 OWNER S MANUAL BEDIENUNGSANLEITUNG M...

Страница 2: ...2 EN 3 19 35 Content Inhalt Contenu EN DE FR...

Страница 3: ...No shore power 230V AC input not available 8 4 2 Frontpanel LED indicators and error modes 8 4 2 1 Error indications 9 4 3 Remote Control 9 4 4 Advanced options 10 4 4 1 Programmable Alarm relay 10 4...

Страница 4: ...reverse polarity by an internal fuse This fuse can only be replaced by authorized personnel Introduction Thank you for purchasing a B TTNER ELEKTRONIK GmbH Inverter Charger Combi ICC Please read this...

Страница 5: ...d loads are now supplied again by the grid generator without any interruption With the Remote Control the charger can optionally be operated in night mode noiseless without fans at half charge power A...

Страница 6: ...The following settings can be made Setting description Factory setting OFF Local External Programming ON External DIP switches 2 to 7 or 9 are ignored and the Inverter Charger Combi will always load...

Страница 7: ...Vollladung LED Battery Full leuchtet dauernd sollte der Batterie jedoch im Netz Betrieb gelegentlich ein vollst ndiger Ladezyklus von 24 Stunden zur Ausgleichsladung geg nnt werden Batterielebensdaue...

Страница 8: ...rely 4 1 2 No shore power 230V AC input not available For using the inverter the unit must be connected to the service battery and a remote switch connected to the remote switch screw terminal of the...

Страница 9: ...gram selection set to Custom while custom made charge program contains an error or time out The Inverter Charger Combi will mostly recover from an error mode automatically when the cause of the error...

Страница 10: ...t the startup current exceeds the overcurrent trip level of the inverter In this case the output voltage will shortly decrease to limit the output current of the inverter If the overcurrent trip level...

Страница 11: ...n bzw schaltet bei defekten zus tzlichen Ladeanlagen Solaranlagen Generatoren o ab Schaltschwelle 15 5 V Verz gerung 20 s R cksetzung durch Batterie 12 75 V 30 s entfernen des Steuersignal D Kl 15 Net...

Страница 12: ...nd 6 for correct settings Incorrect charge current setting Adjust the charge current using DIP 2 and DIP 8 for ICC 3000 Typically the charge current should be set to 10 20 of the total battery capacit...

Страница 13: ...d in inverter mode Try to reduce the ambient temperature around the Inverter Charger Combi Make sure that there is a clearance of at least 10cm around the unit Do not obstruct the airflow place no ite...

Страница 14: ...zu hoher Spann Schaltschwelle 16 5 V automatische R ckkehr 16 5 V berspannungsschutz der BORD Batterie Der BCB sch tzt sich auf der BORD Seite gegen den Anschluss zu hoher Batterie schaltet bei defek...

Страница 15: ...V equipment Parameter AC input voltage range transfer switch Default Value 180V 270V Description Input voltage range which is accepted by the Inverter Charger Combi for feeding through to the connecte...

Страница 16: ...a small generator is used The settings High and Very High can be used when the Inverter Charger Combi is connected to a solid grid or quality generator The factory setting Normal is a good compromise...

Страница 17: ...s high low battery voltage high temperature overload short circuit high ripple voltage and low AC input voltage DC connections Two wires length 1 5 meters 35mm2 M10 bolt terminals AC connections Screw...

Страница 18: ...high AC input voltage applied Reverse connection of battery polarity Connecting wrong batteries too high battery voltages Mechanical stressed enclosure or internals due to harsh handling or incorrect...

Страница 19: ...n 24 4 1 2 Kein Netz vorhanden 230V nicht angeschlossen 24 4 2 Betriebsanzeige LEDs und Fehlermodi 24 4 2 1 Fehler Anzeige 25 4 3 Fernbedienung 25 4 4 Optionale Zusatzfunktionen 26 4 4 1 Programmierba...

Страница 20: ...ohlen wurden kann Br nde Strom schl ge oder Verletzungen verursachen Einleitung Vielen Dank f r den Erwerb einer B TTNER ELEKTRONIK Wechsel richter Ladeger t Kombination Bitte lesen Sie diese Bedienun...

Страница 21: ...eger t w hrend der Wechselrichter deaktiviert wird Die ange schlossenen Lasten werden nun wieder ohne Unterbrechung vom Netz Generator versorgt Mit der Fernbedienung kann das Ladeger t wahlweise ger u...

Страница 22: ...ige Punkte auf Ihre Bed rfnisse zu ndern Folgende Einstel lungen k nnen vorgenommen werden Beschreibung der Einstellungen Werkseinstellung OFF Lokale Externe Programmierung ON extern DIP Schalter 2 bi...

Страница 23: ...l leuchtet dauernd sollte der Batterie jedoch im Netz Betrieb gelegentlich ein vollst ndiger Ladezyklus von 24 Stunden zur Ausgleichsladung geg nnt werden Batterielebensdauer Teilentladene Batterien B...

Страница 24: ...4 1 2 Kein Netz vorhanden 230V nicht angeschlossen F r den Betrieb des Wechselrichters muss das Ger t an der Bord Batterie angeschlossen sein und ein Schalter an der Fernschalterein gangs Schraubklem...

Страница 25: ...er t Bitte zu Kunden dienst einschicken 5 x blinken in Reihe Fehler im Ladeprogramm nur f r charger on LED Anzeige auf Kundenspezifisch aber Ladeprogramm hat einen Fehler Der ICC erholt sich automatis...

Страница 26: ...us einer externen Quelle mit einer gr eren Kapazit t als der des Wechselrichters bezo gen wird Einige Anwendungen wie Motoren oder Pumpen ben tigen beim Anlaufen einen hohen Anlaufstrom In solchen F l...

Страница 27: ...ch tzt sich auf der START Seite gegen den Anschluss zu hoher Spannungen Schaltschwelle 16 5 V automatische R ckkehr 16 5 V berspannungsschutz der BORD Batterie Der BCB sch tzt sich auf der BORD Seite...

Страница 28: ...korrekt eingestellt sind Inkorrekte Ladestrom Einstellung Stellen Sie den Ladestrom mithilfe DIP 2 und DIP 8 ICC3000 ein Normalerweise sollte der Ladestrom auf 10 20 der Gesamtkapazit t der Batterie...

Страница 29: ...selrichter betrieben zu werden Problem M gliche Ursache Abhilfe Die Modusanzeige LEDs inverter on und charger on blinken dreimal pro Sekunde rot Die ICC ist aufgrund zu hoher Temperaturen heruntergefa...

Страница 30: ...ien m glichst ba laden Nur vollgeladene Batterien lagern regelm ig nachladen besonders bei gebra Batterien und bei h heren Temperaturen Batterielebensdauer Tiefentladene Batterien sofort laden Einsetz...

Страница 31: ...wie Computer Uhren und AV Ausr stung besser ist Parameter AC Eingangsspannungsbereich Netzvorrangschalter Wert 180V 270V Beschreibung Der Eingangsspannungsbereich der vom ICC zur Versorgung des anges...

Страница 32: ...n verwendet werden wenn das AC Eingangssignal gest rt oder instabil ist Das k nnte der Fall sein wenn ein kleiner Generator verwendet wird Die Einstellungen Hoch und Sehr hoch k nnen verwendet werden...

Страница 33: ...r Unterspg bertemperatur berlast Kurzschluss hohe Restwelligkeit und niedrige Eingangsspg Anschluss Gleichspag 2 Kabel L nge 1 5 Meter 35mm2 M10 Schraubbolzen Anschluss Wechselspg Schraubklemmblock Ab...

Страница 34: ...ndi gung zu ndern 1 Beispiele f r unsachgem en Gebrauch sind Verwendung zu hoher Eingangsspannungen Umgekehrte Verbindung der Batteriepole Mechanische berlastung des Geh uses oder Innenteile R ckeins...

Страница 35: ...ence de 230V 40 4 2 Modes d erreur et voyants LED de la combinaison convertisseur chargeur ICC 40 4 2 1 Indications d erreur 41 4 3 T l commande 41 4 4 Options avanc es 42 4 4 1 Relais d alarme progra...

Страница 36: ...ndie de choc lectrique ou de l sions corporelles 14 Si le produit est prot g contre la polarit invers e par un fusible interne seul un personnel autoris peut remplacer ce fusible Introduction Merci d...

Страница 37: ...de transfert AC et active l onduleur qui prend en charge l alimentation des charges connect es Tout cela s accomplit si rapidement que m me les charges extr mement sensibles comme les ordinateurs cont...

Страница 38: ...on des param tres Param tre d usine OFF Programmation locale externe ON Externe Les commutateurs DIP 2 7 ou 9 sont ignor s et le ICC chargera syst matiquement les valeurs de param trage ayant t config...

Страница 39: ...BCB entladen Der Ladevorgang kann auf diese Weise jederzeit unterbrochen werden Bei h ufigen Unterbrechungen speziell vor dem Erreichen der Vollladung LED Battery Full leuchtet dauernd sollte der Batt...

Страница 40: ...rement Aucun signal AC ne sera pr sent la sortie du ICC en cas d absence de signal d entr e AC 4 1 2 Pas de pr sence de 230V Pour l utilisation de l onduleur l appareil doit tre connect la batterie de...

Страница 41: ...terie trop basse ou haute tension d ondulation de batterie trop haute d faut de la batterie Deux clignotements la suite Erreur de surcharge AC charge AC n cessitant trop d nergie de l onduleur court c...

Страница 42: ...et augmenter la luminosit des voyants Le mode de nuit peut galement tre interrompu manuellement ou l ICC teint mis en veille par une appuie courte 4 4 Options avanc es 4 4 1 Relais d alarme programmab...

Страница 43: ...Kapazit t nach einigen Lade Entladezyklen wieder zur ckerlangen Batterielebensdauer Batterien k hl halten Einbauort entsprechend ausw hlen berspannungsschutz der START Batterie Der BCB sch tzt sich au...

Страница 44: ...de charge R glez le courant de charge l aide du DIP2 galement DIP8 pour ICC3000 En g n ral le courant de charge doit tre r gl sur 10 20 de la capacit totale de la batterie Trop de perte de tension dan...

Страница 45: ...On et Charger On clignotent en rouge trois fois par seconde Le ICC s est arr t cause d une temp rature trop lev e R duisez la charge de sortie AC en mode onduleur Essayez de diminuer la temp rature a...

Страница 46: ...ba laden Nur vollgeladene Batterien lagern regelm ig nachladen besonders bei gebra Batterien und bei h heren Temperaturen Batterielebensdauer Tiefentladene Batterien sofort laden Einsetzende Sulfatie...

Страница 47: ...ur les charges sensibles comme les ordinateurs les horloges et les quipements audiovisuels Param tre Plage de tension d entr e AC commutateur de transfert Valeur 180V 270V Description Plage de tension...

Страница 48: ...ateur est utilis Les param tres Haut et Tr s haut s utilisent lorsque le ICC est reli un r seau stable ou un g n rateur de qualit Le param tre d usine Normal est un bon compromis qui entra ne toujours...

Страница 49: ...terie basse haute temp rature lev e surcharge court circuit tension d ondulation lev e et tension d entr e AC basse Connexions DC Deux c bles longueur 1 5m de 35mm2 Boulons M10 Connexions AC Bornes vi...

Страница 50: ...e le droit de changer les sp cifications du produit sans pr avis 1 Exemples d usage incorrect Voltage trop important l entr e Inversion des polarit s D g ts internes ou externes dus une mauvaise manip...

Страница 51: ......

Страница 52: ...B ttner Elektronik GmbH Dieselstra e 27 D 48485 Neuenkirchen E Mail info buettner elektronik de Web www buettner elektronik de M O B I L E T E C H N O L O G Y...

Отзывы: