Description of application and parameters
"Detector" application
KNX Technical Manual 2CKA001473B8667
│
06.02.2017
│
77
11.3.35 External push-button parameter — Use of external push-button object
Options:
No
Yes
– No: There is no separate “external push-button” object.
– Yes: A 1-bit “external push-button” communication object (input) is being enabled. Via this
object it is possible to manually change the (output) status of the detector with the aid of a 1-
bit telegram. It is used especially in the "Automatic switch-on" mode for switch-off and in
"Automatic switch-off" mode for switch-on.
11.3.36 External push-button parameter — Use of external push-button switches on with
Options:
On telegram
Off telegram
– On telegram: The detector is activated with a 1 telegram and deactivated with a 0 telegram.
– Off telegram: The detector is activated with a 0 telegram and deactivated with a 1 telegram.
11.3.37 External push-button parameter — Use of switchover to manual mode object
Options:
No
Yes
– No: There is no separate “switchover to manual mode” object.
– Yes: A 1-bit “switchover to manual mode” communication object (input) is being enabled. If
an ON telegram is received on this input, the detector is deactivated. In this case only
manual operation is possible via the "External push-button" object. The receipt of an Off
telegram resets the detector to detector mode.
11.3.38 External push-button parameter — Manual mode is activated with
Options:
On telegram
Off telegram
– On telegram: The detector is deactivated with a 1 telegram and activated with a 0 telegram.
– Off telegram: The detector is deactivated with a 0 telegram and activated with a 1 telegram.