11.3.22 Extended parameter settings — Use of object for test mode
Options:
No
Yes
– No: There is no possibility to set the detector to test mode to test the detection range.
– Yes: There is a separate 1-bit “test mode activation” object (input) for activating the test
mode with a 1. The function is reset again with the receipt of a 0 on this object or
automatically after 10 minutes. During the test mode the LED functions as movement
detection indicator.
11.3.23 Extended parameter settings — Use of the actuator status object
Options:
No
Yes
– No: There is no separate “actuator status” object for connecting with the status of an
actuator.
– Yes: A 1-bit “actuator status” communication object (input) is being enabled. This is
connected with the status of a switch actuator, for example. When this actuator is switched
off via a central command, the detector is informed and is ready again for switch-on after the
pause time.
11.3.24 Extended parameter settings — Use of the status manually on/off object
Note
This parameter is displayed only when automatic switch-on/switch-off has been
activated and/or when the external push-button has been activated.
Options:
No
Yes
– No: The is no separate “status manual on/off” object for monitoring the status of the control.
– Yes: A 1-bit “status manual on/off” communication object (output) is being enabled. This
object sends an On telegram when the movement detector is deactivated and only one
manual operation is possible via the “external push-button” input. If this object sends an Off
telegram, the movement detector switches back to automatic mode.