Description of application and parameters
"Constant light controller" application
KNX Technical Manual 2CKA001473B8667
│
06.02.2017
│
108
11.5.46 Enable — At enable, output sends
Options:
Current output value
Start value
– Current output value: During enable it is checked whether a movement has taken place. If
yes, the lighting is switched on. If no, the lighting is switched off.
– Start value: During enable it is checked whether a movement has taken place. If yes, a
switch-on takes place with a start value. If no, 0% is sent and not the parameterised start
value.
11.5.47 Enable — Output sends at blockage
Options:
No telegram
OFF after expiration of the light-on time
Single value for switching off
– No telegram: No telegram is sent during blockage.
– Off after expiry of switch-off delay: During blockage the switch-off delay is started anew and
the detector sends the value that is parameterised under the “value for switch-off” parameter
only after this time has expired.
– Single value for switch-off: During enable the single value which has been parameterised
under the “value for switch-off” parameter is sent.