Description of application and parameters
"Constant light controller" application
KNX Technical Manual 2CKA001473B8667
│
06.02.2017
│
107
11.5.42 Sensor selection — Use of sensors 1 - 4
Options:
Yes
No
– Yes: This sensor is active and detects movement.
– No: This sensor is switched off and movement is no longer detected in this area.
11.5.43 Enable — Presence detector enable object
Options:
No
Yes
– No: There is no object with which the constant light controller can be blocked or enabled.
– Yes: A 1-bit “enable presence” communication object (input) is being enabled. This object
allows the constant light controller to be enabled or blocked. No telegrams are sent by the
detector during blockage.
11.5.44 Enable — Enable with
Options:
ON telegram
OFF telegram
– On telegram: With the receipt of value 1 on the “enable movement” (input) object, the
detector is enabled and blocked with value 0.
– Off telegram: With the receipt of value 0 on the “enable movement” (input) object, the
detector is enabled and blocked with value 1.
11.5.45 Enable — After bus voltage recovery, presence detector is
Options:
Enabled
Blocked
– Enabled: The device is enabled and functions normally when the bus voltage is interrupted
or the device has been reprogrammed, as well as after a reset.
–
Blocked: The device is blocked and must be enabled for normal function when the bus
voltage is interrupted or the device has been reprogrammed, as well as after a reset.