11.8.73 Setpoint settings — Setpoint temperature for heating comfort (°C)
Options:
Setting option between 10 - 40
Specifies the comfort temperature for heating when people are present.
Note
This parameter is only available when the "Control function" parameter is set on
"Heating" or "Heating with additional stage".
11.8.74 Setpoint settings — Reduction for standby heating (°C)
Options:
Setting option between 10 - 40
Specifies the temperature in heating mode when nobody is present. On devices with a display,
this mode is indicated by the standby icon.
Note
This parameter is only available when the "Control function" parameter is set on
"Heating," "Heating with additional stage," "Heating and cooling" or "Heating and
cooling with additional stages".
11.8.75 Setpoint settings — Reduction for ECO heating (°C)
Options:
Setting option between 0 - 15
Specifies the temperature in heating mode when nobody is present. On devices with a display,
this mode is indicated by the ECO icon.
11.8.76 Setpoint settings — Setpoint temperature for frost protection (°C)
Options:
Setting option between 5 - 15
Function for protecting the building against the cold. On devices with a display, this mode is
indicated by the frost protection icon. Manual operation is blocked.
Note
This parameter is only available when the "Control function" parameter is set on
"Heating," "Heating with additional stage," "Heating and cooling" or "Heating and
cooling with additional stages".