Description of application and parameters
"Constant light controller" application
KNX Technical Manual 2CKA001473B8667
│
06.02.2017
│
100
11.5.14 Extended parameters — Value for reduced brightness (%)
Options:
0 .. 20 .. 100
Yes
Here the value for the reduced brightness is set. After the switch-off delay has expired the
detector is to dim the light to this value.
Switch-off value
≤
bottom control limit
≤
reduced brightness < upper control or dimming limit.
11.5.15 Extended parameters — Brightness reduced according to switch-off delay (hh:mm:ss)
Options:
00:00:10 .. 00:05:00 .. 18:12:15
– Here the value for the switch-off delay of the reduced brightness is set. The total switch-off
delay then consists of the switch-off delay + brightness reduced according to switch-off
delay.
Used movement detection
Options:
Internal only
External only
Internal and external
– Only internal: The presence detector responds only to movement measured internally.
– Only external: The presence detector responds only to telegrams that are received via the
“slave” object (input).
– Internal and external: The presence detector responds to movements measured internally
and to external telegrams that are received via the “slave” object (input).
11.5.16 Extended parameters — Slave sent
Options:
Cyclic On telegram
On/off telegram
– Cyclic On telegram: The presence detector, which is connected to the master as slave,
sends only On telegrams cyclically.
– On/Off telegram: The presence detector, which is connected to the master as slave, sends
only On/Off telegrams.