Operating the Controls
Operating the Controls
6.3.10.1 Installer (+) Parameter List
The following values will be displayed and can be changed. Values with the
sym-
bol cannot be changed!
Index
Parameter
Description
Area
Default
V1042
Esys2042
1
CH Slope
Central factor for the ascent/des-
cent of the edge; defines the tem-
perature rise in the warm-up
cycle of the central heating de-
mand
0-60 °C/Min.
5 °C/Min
5 °C/Min
2
CH Anticycle
Time
Central heater anti-cycling time.
During this period the CVBC will
not accept any further central
heating demands.
0-900 sec.
90 Sec.
2 min.
3
CH Kp
Proportional control factor central
heater
0-255
3
3
4
CH Ki
Integral control factor central
heater
0-255
95
95
5
DHW Kp
Proportional control factor for the
drinking-water heater
0-255
5
5
6
DHW Ki
Integral control factor for the
drinking-water heater
0-255
95
95
7
Ignition
Level
Ignition level with which the boiler
is ignited
30-100 %
50%
33%
8
Fan Kp
Proportional control factor for the
fan controller
0-255
13
13
9
Fan Ki
Integral control factor for the fan
controller
0-255
150
150
11
CH set-point
The actual set-point of the
central heater
30-80 °C
80 °C
70 °C
12
CH Pump
Overrun
Pump overrun time for the central
heater
1-20 Min.
7 Min.
7 Min.
13
DHW set-
point
The actual set-point of the drink-
ing-water heater
35-65 °C
60 °C
55 °C
14
CH max. ca-
pacity
The maximum capacity of the
central heater
60-100%
90%
87%
- 34 -