Malfunctions and Errors
Malfunctions and Errors
7.3
Error history Mode
The Error history mode can be activated by holding
the 3 button longer than 3 seconds. The informa-
tion’s displayed format is shown in the following
table
III
L
E
D
3
T
a
s
t e
3
Display
Display Element
E-Symbol alternating with the
Index-Symbol
Segment B
alternating
Error code for the chosen index
Segment C and D
Error Log Mode
LED 3 = Blinking
blinking
Error log mode can be exited by quickly pressing the 3 button (less than 1 second).
Error log mode also has a time out function that exits the installer mode after 30
minutes of inactivity. This function is also turned off if the electrical supply is interrup-
ted.
7.4
Log Resistance Values for the Boiler and Reservoir Sensors
If there is an error in the boiler or reservoir sensors’ transmittal, it can be determined
via the sensors’ resistance values.
Temperature °C
Nominal Value k
RT 2333 640 6123
Temperature °C
Nominal Value k
RT 2333 640 6123
-40
309,5
35
8,055
-35
229,4
40
6,653
-30
171,7
45
5,524
-25
129,7
50
4,609
-20
98,82
55
3,863
-15
75,94
60
3,253
-10
58,82
65
2,752
- 5
45,91
70
2,337
0
36,10
75
1,994
5
28,59
80
1,707
10
22,97
85
1,467
15
18,29
90
1,266
20
14,72
95
1,096
25
12,00
100
0,9522
30
9,805
- 39 -