Mounting / Installation
Mounting / Installation
5.5.2 Gas Throughput Table / Connection Pressure
Gas Type
Load Area
Gas Flow rate
(l/min)
Connection
Pressure
Min.
Max.
LL(L)-Gas
5,1 – 22,8 kW
11,6
50,1
20 mbar
E(H)-Gas
5,1 – 22,8 kW
10,0
43,3
20 mbar
Liquid Gas
5,1 – 22,8 kW
8,0
34,6
50 mbar
Heating value: Natural Gas LL(L) = 8,83kWh/m³; Natural Gas E(H) = 10,22 kWh/m³; Liquid Gas = 12,78 kWh/m³
The above gas type values may vary regionally. Please ask your energy provider for
the heating values as necessary.
5.5.3 Changing Gas Types
Changing gas types does not require any adaptations to the unit. Simply adjust the
CO
2
Level (Ch. 5.5.1) to the respective gas type.
- 27 -