Operating the Controls
Operating the Controls
Index
Parameter
Description
Area
Default
V1042
Esys2042
15
1-10
4-5
16
DHW Pump
Overrun
Pump overrun time for the drink-
ing-water heater
30-180 Sec.
30 Sec.
30 Sek.
17
CH Hyster-
esis
Hysteresis of the central heater’s
set-point during modulation
2-10 °C
3 °C
7 °C
18
DHW Hys-
teresis
Hysteresis of the drinking-water’s
set-point during modulation
2-10 °C
7 °C
7 °C
19
CH Max.
Set-point
Maximum value at which the
central heater’s set-point may be
set
30-85 °C
85 °C
80 °C
The values can be changed with the 6 and 7 but-
tons, respectively.
6
7
L
E
D
5
T
a
s
t e
T
a
s
t e
When changing the value, the LED 3 will blink,
which shows that the value can be confirmed by
pressing the 3 button. If the value has not been
confirmed within 5 seconds, the original value is re-
stored and no new value will be saved.
III
L
E
D
3
T
a
s
t e
3
LED blinkt
Installer (+) mode will be exited after one 1 min. of inactivity. If LED 3 is off, installer
(+) Mode can also be exited by quickly pressing the 3 button (less than 1 second).
- 35 -