Mounting / Installation
Mounting / Installation
4.2.5 General Instructions for the Gas Connection
•
The gas connection must be connected in accordance with the current
regulations. Installation may only be performed by a licensed profes-
sional!
•
Make sure there is no open fire, flammable materials or the like in close
proximity to the installation location. LIFE THREATENING DANGER!
•
Before installation, check to make sure the gas meter has adequate
capacity. Take the usage of all household appliances into account.
Let your energy provider know if your line does not have a high
enough capacity.
•
Make sure the gas lines are clean. Clean the gas lines with high pres-
sure or by knocking them clean before installation.
•
An approved shut-off valve with a fire protective faucet must be instal-
led in front of the boiler.
•
Preferably, you can also install a gas filter to keep the gas control
valve from getting dirty.
4.2.6 Connecting the Gas Main
Please follow these instructions during installation:
•
The main gas spigot must be shut off before the work begins. If the
connection is older, make sure the spigot still closes to avoid uncon-
trolled gas leaking out.
•
Secure the line against accidental start up while you are working on
the lines.
•
Make sure the fire protective faucet is mounted properly.
•
Before start up, make sure the entire gas line is sealed, especially at
connection points. The gas faucet and the gas line may not exceed a
maximum pressure of 150 mbar.
•
Ventilate the gas line after attaching to avoid malfunctions!
•
Ventilate the room well after installation to disperse any gas that may
have escaped.