60
Troubleshooting
Type 8745 Ethernet, 8745 Analogue
12.1.5
Product status indicator is orange
(MFM Analogue)
A calibration procedure is in progress.
→
Wait until the calibration procedure is completed.
12.1.6
Product status indicator is orange
(MFM Ethernet)
Identify the cause:
1.
A calibration procedure is in progress.
→
Wait until the calibration procedure is completed.
2.
If the PROFINET protocol is used, then the PLC is in Stop
mode.
12.1.7
Product status indicator is orange
(MFC Analogue)
Identify the cause:
1.
A calibration procedure is in progress.
→
Wait until the calibration procedure is completed.
2.
The Autotune is in progress.
→
Wait until the Autotune is completed.
3.
The parameter
set-point value source
is set to one of the
following choices:
•
Open-loop control mode
•
manual set-point value
•
analyze system
12.1.8
Product status indicator is orange
(MFC Ethernet)
Identify the cause:
1.
A calibration procedure is in progress.
→
Wait until the calibration procedure is completed.
2.
The Autotune is in progress.
→
Wait until the Autotune is completed.
3.
The parameter
set-point value source
is set to one of the
following choices:
•
Open-loop control mode
•
manual set-point value
•
analyze system
4.
If the PROFINET protocol is used, then the PLC is in Stop
mode.
12.1.9
Product status indicator is yellow
(MFM Analogue)
One of the following values is out of specification. The sensor or
the product can be damaged.
•
the fluid temperature
•
the product temperature
•
the supply voltage
→
Operate the product within the specifications. If the product
status indicator is still yellow, then send the product back to
Bürkert.