Technical data
Type 8745 Ethernet, 8745 Analogue
6.7.4
Quality of the operating fluid
Use the operating fluid that is given on the product Type-label.
The operating fluid must be clean and dry.
The gas or gas mixture must obey the quality criteria
in Tab. 19. The quality criteria are given in standard
ISO 8573-1, Compressed Air - Part 1: Contaminants and
purity classes. The operating gas must obey the quality
criteria to obey the following requirements:
•
the necessary measurement accuracy of the product
•
to meet the safety requirements
•
to meet the closed-loop control accuracy of an MFC
For further information on the quality criteria, refer to
ISO 8573-1.
Tab. 19:
Quality criteria of the fluid
Criteria
Quality class Value
Maximum particle size
2
1 μm
Maximum particle density
2
1 mg/m³
Maximum dew point under
pressure
4
3 °C
Maximum oil concentration
1
0.01 mg/m³
6.8
Pressure loss (MFM)
A Mass Flow Meter has a pressure loss that depends on the fol
-
lowing parameters:
•
the flow rate value
•
the size of the product fluid-connections
•
the type of the product fluid-connections
•
the size of the product base-block
•
the type of operating gas
→
Determine the pressure-loss value depending on whether the
operating fluid is air or a gas other than air.
6.8.1
Operating gas is air
If the operating gas is air, then read the pressure-loss value
directly from the diagrams in Fig. 13 or in Fig. 14.
For example, if the flow rate through an MFM with 1/2" threaded
fluid-connections is 1400 l
N
/min then the pressure loss for air, as
, is 140 mbar.