31
Technical data
Type 8745 Ethernet, 8745 Analogue
6.9
Electrical data
6.9.1
Product variant Ethernet
WARNING
▶
For UL-certified components, only use limited power circuits
of "NEC Class 2".
Tab. 20:
Electrical data of an MFM
Operating voltage
24 V DC ±10 %
Maximum power
consumption
4 W
Communication
interface
PROFINET, EtherNet/IP, EtherCAT,
Modbus TCP
Tab. 21: Electrical data of an MFC
Operating voltage
24 V DC ±10 %; residual ripple < 2 %
Maximum power
consumption
Refer to the Type label
Communication
interface
PROFINET, EtherNet/IP, EtherCAT,
Modbus TCP
6.9.2
Product variant Analogue
Tab. 22:
Electrical data of an MFM with D-sub DE-9 male connector
Operating voltage
24 V DC ±10 %
(15 V DC ±10% on request)
Maximum power consumption 2 W
Digital input
•
0...0,2 V
•
to activate level 1
•
1...4 V or open
•
to activate level 2
•
5...28 V
•
to activate level 3
Set-point analogue output
•
0/4...20 mA
•
Maximum loop impedance:
600
W
at an operating
voltage of 24 V DC (200
W
at an operating voltage of
15 V DC)
;
Resolution: 20 µA
•
0...5/10 V
•
Maximum current: 20 mA
Resolution: 10 mV
Relay output
Normally closed contact (break
contact), free of potential
English