24
Technical data
Type 8745 Ethernet, 8745 Analogue
6.4
Markings
WARNING
Risk of injury caused by pressure, fluid escape.
Important product-specific data is indicated on the Type label
and the calibration plate.
▶
Only use the product for the specified operating fluid.
▶
Do not exceed the specified calibration pressure.
6.4.1
Calibration plate
5
4
3
2
1
6
Mass Flow Controller
Medium 1 Medium 2
P1: 1,00 barg P1: 1,00 barg
Mounting: horizontal upright
Id: 00******
QC passed: __ . __ . ____
1. Product variant
2.
Calibration fluid
3.
Calibration pressure
4.
Installation position
5. Product article number
6. Calibration date
Fig. 8:
Description of the calibration plate
6.4.2 Type label
874x 24V ... 11W [7,5W]
IP20 NEC Class 2 only
5,0 Nl/min Air
10,0 Nl/min Air
Profinet 10/100Mbit/s
GR:1 KL:A Ta=-10°C..+50°C
S/N 1000 W41ME PS=100barg EPDM
00******
1
2
3
4
5
6
7
8
10
11
9
12
13
14
15
16
1.
Type of the product
2.
Supply voltage, direct current
3.
Consumption according to UL 61010-1 [proportional valve:
typical consumption
1)
; motor valve: power consumption
1)
to hold the position of the motor valve]
1)
Conditions: ambient temperature 23 °C, nominal flow rate
100%, regulation for 30 minutes
4.
Warning symbol: Observe the Operating Instructions that
are delivered with the product.
5.
Ambient temperature
6. Sealing material
7.
Burst pressure
8. Manufacturing code
9. Class of the control valve according to the DVGW (Deut-
scher Verein des Gas- und Wasserfaches)
English