3
Regulations, standards and guidelines
Logano plus SB615 Gas - We reserve the right to make any changes due to technical modifications.
9
3
Regulations, standards and guidelines
During installation and operation of the system, standard
engineering practices, the buildings regulations and any
legislative requirements must be observed.
3.1
Low water indicator installation
B
For boilers > 300 kW, install a low water indicator,
following the manufacturer's technical documents for
installation and operation.
B
If the LWI connection provided is not used for the
installation of an SYR 932.1 low water indicator
(Buderus accessory), seal the connection off with a
plug (
Æ
Chapter 5.6, page 15).
The Logamatic control system is used for this boiler.
3.2
Standards and guidelines/directives
This device meets all basic requirements of relevant
European standards and guidelines:
• 90/396/EC Gas Appliance Directive
• EN 677, EN 303-1, EN 303-3, DIN 4702-6, EN 267,
EN 303-2
• 92/42/EC Efficiency Directive
• 2006/95/EC Low voltage Directive
• 2004/108/EC Electro Magnetic Compatibility
Directive
• 97/23/EC Pressure equipment Directive
Standard: TRD 702
Observe the following during installation and
operation:
• Local Building Regulations concerning boiler room
installations
• Local Building Regulations regarding air supply and
extraction equipment as well as connection to a flue
• Latest edition of the IEE Wiring regulations governing
electrical connection to the mains power supply
• The technical rules of the gas supply utility regarding
the connection of the gas burner to the local mains gas
supply
• Regulations and standards regarding the safety
equipment in water-filled heating systems
• Installation instructions for heating engineers
• In Belgium, the standards NBN D 30-003,
NBN D 51-004 and addenda must be observed.
• In the Netherlands, technical rules, building regulations
and other legal requirements (e.g. NEN 1078 (GAVO),
NEN 3028 and NEN 1010) must be observed when
installing and operating the system.
• In Austria, observe local building regulations as well as
ÖVGW Directive G1 or G2 (ÖVGW-TR gas or LPG)
during installation. The requirements of the national
directive Article 15a B-VG, regarding emissions and
efficiency, are fulfilled.
• For Switzerland:
By carrying out measurements at the installation
location, it must be checked whether the LRV maximum
permitted limits concerning CO and NOx are being
observed. The boilers have been tested according to
VKF fire safety regulations. During installation, observe
the guidelines for installing and operating gas-fired
boilers G3 d/f, the gas guidelines G1 SVGW, and local
fire safety regulations in force within the canton.
The output figures shown in the tab. "Specifications"
are nominal output figures.
In practice, these values will sometimes not be reached
within the specified output range in order to adhere to
LRV regulations.
Permissible fuels
Logano SB615 Gas and Logano plus SB615 VM gas
condensing boilers can be operated using the following
fuels:
• Natural gas and liquid propane (LP) according to
DVGW (German certification body) worksheet G 260
• Natural gas and liquid propane (LP) supplied by public
gas utility (Austria, Switzerland)
B
Only use burners that are compatible with these gas
types.
B
Observe the specifications of the burner supplier.
Observe all standards and guidelines
applicable to the installation and operation of
this system in your country!
The details on the boiler rating plate are
definitive and must be observed.
For UK & Ireland:
B
For boilers > 300 kW, install a low water
indicator as required by BS-EN 12828.
B
For installation and operation, refer to the
technical documents provided by the
manufacturer.
For Poland:
B
For boilers > 100 kW, equip the boiler
with a low water indicator as required by
PN-91/B-2414 (p2.5).