8
Inspection/maintenance
Logano plus SB615 Gas - We reserve the right to make any changes due to technical modifications.
40
8.3
Cleaning the boiler
B
Remove upper and lower front panels.
B
Remove the front thermal insulation.
B
Undo the door bolts and open the burner door.
Fig. 29 Removing the front panel and thermal insulation
B
Loosen nuts from the clamping angle, swivel the
clamping angle away and remove the return bonnet.
B
Clean the combustion chamber and the heating
surfaces.
Fig. 30 Removing the return hood and opening the
burner door
DANGER:
Risk of injury due to burner door
falling off when opened!
B
Make sure that both hinge bolts
(
Æ
Fig. 7, [1], page 18) are inserted.
CAUTION:
Boiler damage due to not using
the appropriate cleaning equipment!
B
Only Buderus cleaning equipment may be
used for cleaning.
For wet-cleaning, we recommend
high-pressure cleaning equipment.
B
Do not pour cleaning residues through the
neutralisation device.
B
Do not block up the condensate drain
(
Æ
Fig. 32, page 42) when cleaning.