Technical Information
3
Logano G125 BE - Specifications subject to change without notice.
10
3.2.2 Requirements for Boiler Room and Surroundings
3.2.3 Combustion Air Requirements
3.2.4 Fuel Conditions
Operating Conditions
Comments – Detailed Information
Boiler room temperature
+40 to +104 °F
Relative humidity
max. 90 %
No condensate or dampness in boiler room.
Dust
–
No excess amounts of dust should be present in the boiler room, e.g.:
–
No sheet rock or construction dust.
The available combustion air can not contain dust or other particles/ use of an air
filter might be needed, e.g.:
–
Combustion air from nearby roads with high dust levels.
–
Combustion air from nearby production facilities such as chemical plants &
shops.
–
Airborne particulates.
Halogenated Hydrocarbons
contamination
–
Combustion air must be free of halogenated hydrocarbons components.
–
Eliminate any chemical compound such as paints, lacquers, thinners, clean-
ing agents. If not possible, provide fresh outside air for combustion.
Please observe the following:
–
Product information of Buderus catalog.
–
Also observe guidelines in K3 chapter of Buderus catalog.
Fans, removing air from boiler
room
–
Avoid forced air removal by mechanical means during boiler operation such as:
–
Bathroom exhaust fans
–
Dryer
–
Air-conditioning equipment
Animals
–
The boiler room and especially the air inlet openings for combustion air must be
kept free from animals entering by means of grills.
Fire Protection
–
Maintain proper clearances to combustible materials as required per local code.
Maintain a minimum distance of 16”. Do not store flammable materials near the
boiler.
Flood Zone Conditions
–
Separate the fuel supply and electrical power supply from the boiler during flood
conditions. Replace the boiler components such as insulation, electrical and con-
trol components afterwards.
Table 4 Boiler room and surroundings
Operating Conditions
Boiler capacity (combine total boiler ca-
pacity for multiple units)
Cross area required
Two air inlet openings from out-
side: one top, one near bottom
< 170,000 Btu/hr
At least 43 square inch
> 170,000 Btu/hr
At least 43 square inch plus 2.5 square inch per 10,000
Btu/hr, if the output is higher than 170,000 Btu/hr.
Table 5 Observe local codes and regulations for combustion air requirements
Country
All Countries
Fuel
#2 Fuel Oil ASTM D396-05 Type 2
Comments
No other fuel may be used with this burner.
Burner requires annual service and cleaning. Verify each time that the complete heating system is in working
order. Defects must be remedied immediately.
Table 6 Permitted fuel types