Placing the Boiler
6
Logano G125 BE - Specifications subject to change without notice.
15
6
Placing the Boiler
This chapter discusses how to place the boiler in the
boiler room.
6.1
Clearances
Position the boiler while observing the clearances in
(
Î
Fig. 7). Access to the boiler is reduced when reduc-
ing these clearances.
The boiler foundation must be level and sufficiently
strong.
The burner door is factory installed right swinging. You-
can reverse the door swing in the field.
CAUTION!
SYSTEM DAMAGE
due to freezing temperatures
z
Place the boiler in a frost free room.
Fig. 7
Clearance dimensions for G125 boilers
Distance
A
Recommended
51 1/8"
minimum
39 3/8"
B
Recommended
27 1/2"
minimum
15 3/4"
C
Recommended
15 3/4"
minimum
3 7/8"
L
see Chapter 3 „Technical Information“
Table 10 Recommended and minimum clearances
(Measurement in Inches)
NOTICE
Smaller clearances must abide with state
and local code. The boiler is approved for
6" side clearances. A minimum distance
of 18" to combustible materials must be
maintained per NFPA 31.
Floor material must comply with
NFPA 31.
NOTICE
Observe required distances to other com-
ponents such as water piping, venting
and other components.