Placing the Boiler in Operation
8
Logano G125 BE - Specifications subject to change without notice.
43
When you determine that the stack temperature is too
low, and condensate formation might take place in the
chimney, the stack temperature can be increased by the
following steps:
–
Adjust the flue baffles
–
Remove the flue baffles
–
Remove flue blocking plates
z
Shut-off the boiler (
Î
Chapter 9, page 47).
z
Remove burner cover from boiler (
Î
Chapter 5.1,
page 13).
8.8.1 Adjusting/Removing Flue Baffles
Adjust or remove the flue baffles always in pairs.
z
Remove burner cable from burner connector.
z
For sealed combustion operation, remove hose from
burner intake connection.
z
Open burner door by removing the two hex head
bolts.
z
Close burner door and secure with burner door bolts
(ca. 90 Lbs/inch). Tighten bolts evenly.
WARNING!
DANGER TO LIFE
from electric shock.
z
Prior to opening the burner: Shut off
power supply and prevent from acci-
dental reactivation.
CAUTION!
BURNING DANGER
due to touching of hot surfaces.
z
Wear thermal protective gloves or use
a set of pliers.
Fig.43
Adjusting the flue baffles