BC10 basic controller
10
Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007
43
We reserve the right to make any changes due to technical modifications!
Buderus • http://www.buderus.net
z
Turn the knob to set the maximum space heating system
temperature.
z
Press the "Chimney Sweep"
d
button to exit manual
mode.
10.3 Configuring the boiler
10.3.1 Adjusting the heating capacity
Setting the heating capacity depending on the maximum
heat requirement (see table 9).
z
Press and hold the "Chimney Sweep"
d
and "Service"
e
buttons until an "L" with a double-digit value (e. g.
L80
) or an "L" followed by two dashes (
L--
) is displayed.
Factory setting "
L--
".
z
Set the heating capacity by pressing the "Chimney
Sweep"
d
button (higher values) or the "Reset"
c
button (lower values).
z
Press the "Service"
e
button to confirm the setting.
190
170
150
130
90
110
Regu-
lator
setting
in %
Heating capacity (±5 %)
boiler cap.
24 kW
boiler cap.
30 kW
boiler cap.
45 kW
boiler cap.
60 kW
kW
btu
kW
btu
kW
btu
kW
btu
L30
7.2
24,566
8.7
29,684 13.5 46,062 18.0 61,542
L40
9.6
32,755 11.7 39,920 18.0 61,416 24.0 82,080
L50
12.0 40,944 14.8 50,498 24.5 83,619 30.0 102,630
L60
14.4 49,133 17.8 60,734 27.0 92,178 36.0 123,192
L70
16.8 57,322 20.9 71,311 31.5 107,573 42.0 143,766
L80
19.2 65,510 23.9 81,547 36.0 122,976 48.0 164,352
L90
21.6 73,699 27.0 92,124 40.5 138,389 54.0 184,950
L--
24.0 81,888 30.0 102,360 45.0 153,810 60.0 205,560
Table 9
Heating capacity
WARNING
– Turn the "space heating system
temperature" knob to limit the heating
system temperature to the permissible flow
temperature for the floor heating circuit (e. g.
86 – 104 °F = 30 – 40 °C), so pipes will not
overheat.
DANGER
The heating system can freeze up if a power
failure occurs or after switching off the power
supply, because manual operation then is no
longer active.
– You must re-activate manual operation after
switching on the system to keep the heating
system operational (especially if there is a
risk of frost).
+
L--
/